Installation Instructions

13
Instructions for the installer
2.4.1 - PERFORMANCE DATA ErP DIRECTIVE
MODULEX
EXT100 EXT150 EXT200 EXT250 EXT300 EXT350
Element Symbol Unit
Effective nominal output Pnominale kW 97 146 195 244 294 342
Seasonalenergyefciencytoheat
the room
ƞ
s % 92 92 92 92 92 92
Season efciency class to
discharge
A A A A A A
For boilers to heat the room
and mixed boilers: useful heat output
Useful heat output with
high temperature capacity
(Tr 60 °C / Tm 80 °C)
P
4 kW 97,2 146,1 195,2 244,5 294,0 341,7
Ratedheatoutputefciency
with high temperature capacity
(Tr 60 °C / Tm 80 °C)
ƞ
4 % 88 87,7 87,7 88,1 88,3 88,5
Useful power at 30% of the rated heat
output with low temperature
capacity (Tr 30 °C)
P
1 kW 32,2, 49,3 64,4 80,5 96,6 112
Performance at 30% of the rated heat
output with low temperature
capacity (Tr 30 °C)
ƞ
1 % 96,7 96,7 96,7 96,7 96,7 96,7
Boiler with output range adjustment:
YES / NO
NO NO NO NO NO NO
Auxiliary electricity consumption
With a full load elmax kW 0,145 0,210 0,290 0,362 0,435 0,507
With a partial load elmin kW 0,040 0,040 0,040 0,040 0,040 0,040
Standby mode P
SB kW 0,010 0,010 0,010 0,010 0,010 0,010
Other elements
Heat dispersion on standby P
stb kW 0,787 0,94 0,98 1,10 1,15 1,39
Nitrogen oxides emissions NOx
Mg/kWh
54 54 54 54 54 54
For mixed heating appliances
Declaredloadprole - - - - - -
Waterheatingenergyefciency ƞ
wh % - - - - - -
Daily consumption of electricity Qelec kWh - - - - - -
Daily consumption of fuel Qfuel kWh - - - - - -
Internal sound power level Lwa dB (A) - - - - - -
Seasonal DHW efciency class
- - - - - -
*