INSTALLATION Wall Mounted 0121…0661 MONOBLOC EXTERNAL UNITS FOR INSTALLATION IN SHELTERS AND PREFABRICATED BUILDINGS WMA/WMF 0121- 0181 - 0251 - 0281 - 0331 0551 - 0661 INSTALLATION MANUAL GB © UNIFLAIR 2000 Monobloc Wall Mounted Unit - WMA/WMF 0121-0181-0251-0281-0331-0551-0661 - Rev. 2.0.
INSTALLATION Wall Mounted 0121…0661 Before installing or carrying out any operation on the unit, carefully read the instructions and safety regulations in this manual and on the notices on the unit. Some characteristics of special-order units may be different from those described in this manual. UNIFLAIR ITALIA S.r.l. Via dell’Industria, 10 35020 BRUGINE (Padova) Italy Tel. +39 (0)49 9713211 Fax. +39 (0)49 5806906 Internet: www.UNIFLAIR.com E-Mail: info@UNIFLAIR.com Release: 2.
INSTALLATION Wall Mounted 0121…0661 Index Page Symbols Important warnings Access to main components Transport and movement Dimensions and weights Positioning the unit Air distribution Mounting the unit Connecting the condensate drain Electrical connections Recommended power supply cable sections and line fuses Temperature and humidity sensor (optional) 3 4 5 7 8 9 10 13 15 16 20 22 SYMBOLS SYMBOL MEANING DANGER SYMBOL MEANING MOVING COMPONENTS IMPORTANT WARNING HOT SURFACE BURNING – LIVE COMPONEN
INSTALLATION Wall Mounted 0121…0661 This unit has been subjected to risk analysis under EC Directive 98/37/CEE (89/392/CEE): it is built to perform the functions for which it was designed without risk as long as the installation, operation and maintenance of the unit are all carried out according to the instructions in this manual and on the labels on the unit. The risks which are particularly important for the safety of the user are marked with the danger symbol.
INSTALLATION Wall Mounted 0121…0661 ACCESS TO MAIN COMPONENTS The unit is accessible on all sides by removing the relevant panels. Important: before opening the unit disconnect the power supply and wait for the fans to stop and wait for the electric heating element to cool. A D Q.E. B T S C WM* 0121-0181-0251-0281-0331 Fig. 1 TOP FRONT PANEL (A) The Top Front Panel is fixed with two screws; removing it gives access to the electrical panel.
INSTALLATION Wall Mounted 0121…0661 A D Q.E. B B C C WMF 0551-0661 Fig. 2 TOP FRONT PANEL (A) The Top Front Panel is fixed with two screws; to remove: - release the bolts; - hold edges of upper panel and pull; - raise the panel to remove. This operation gives access to the airfilter; free-cooling damper, damper motor and electrical panel. Access to the radial fan and the pre-heat electrical resistors is only possible once the internal sheet is removed (D).
INSTALLATION Wall Mounted 0121…0661 TRANSPORT AND MOVEMENT The unit should not be turned on its back or upside-down, or exposed to the weather and should be taken as near as possible to the installation location before removing the cardboard packing and the pallet. The unit can be lifted: - with a fork-lift, placing the forks in the appropriate slots of the pallet; - with straps passed under the unit, making sure that they do not put pressure on the upper rim of the unit.
INSTALLATION Wall Mounted 0121…0661 DIMENSIONS AND WEIGHTS mm A1 B C Sx (*) Dx (*) H (*) E (*) kg WM 0121 WM 0181 WM 0251 WM 0281 WM 0331 650 650 930 930 930 1790 1790 1940 1940 1940 400 400 450 450 450 300 300 300 300 300 400 400 400 400 400 300 300 300 300 300 1500 1500 1500 1500 1500 135 152 190 190 210 B (*) see par. ‘WORKING SPACE’ A1 E C Fig. 4 Sx Dx H Sx Dx Dx H Fig.
INSTALLATION Wall Mounted 0121…0661 mm WMF 0551 WMF 0661 A1 B C Sx (*) Dx (*) H E (*) 1050 1050 2250 2250 kg 625 625 300 300 300 300 300 300 1500 1500 300 320 B (*) see par. ‘WORKING SPACE’ C A1 E Fig. 6 Sx Dx H H Fig. 7 WM* 0551-0661 POSITIONING THE UNIT WM units are designed to be installed outdoors. However, it is recommended to protect the unit from rain, snow or water falling from drains or gutters.
INSTALLATION Wall Mounted 0121…0661 To facilitate maintenance, leave at least 1,5m free space in front of the unit as shown in the diagram (point E). This minimum distance allows the expulsion of external air for condensation and the aspiration of air for free-cooling. N.B.:Side access to the unit is only necessary on the right side of models 0121…0331 for the replacing of the damper servomotor; it is not necessary for other maintenance operations or access to electrical panels and wires.
INSTALLATION Wall Mounted 0121…0661 mm WM 0121 A1 B1 C1 D1 E1 F1 G1 H1 L1 A2 B2 C2 E2 F2 L2 WM 0181 WM 0251 WM 0281 WM 0331 WM 0551 WM 0661 50 30 128 430 470 404 850 880 1138 70 70 135 230 280 240 230 280 340 710 990 1110 1790 1940 2250 570 850 840 45 25 123 420 460 394 845 875 1133 240 290 250 240 290 350 580 860 850 A1 E1 A2 E2 B1 B2 F2 L2 F1 H1 D1 L1 D1 C2 L2 Rear of the unit C1 G1 Outside wall of the air conditioned environment Fig.
INSTALLATION Wall Mounted 0121…0661 Fix rubber seals around the mouths of the air intake and discharge to ensure an airtight fit; 18-20mm thick selfadhesive closed-cell neoprene rubber tape is recommended. Apply a layer of builder’s silicone to the joint between the top cover of the unit and the wall, to prevent rain from entering the gap. SILICONE SEALANT NEOPRENE TAPE Fig.
INSTALLATION Wall Mounted 0121…0661 MOUNTING THE UNIT WM units are mounted on the outside wall of the air conditioned environment and fixed using screws through the two side flanges. Before installing the unit observe the following instructions: 1. Check that the wall is of suitable material and strength to support the weight of the unit and to cope with the (relatively minimal) vibrations of the refrigerant compressor; 2. Make intake and discharge holes in wall (see par. 'AIR DISTRIBUTION'; 3.
INSTALLATION Wall Mounted 0121…0661 6. If the units are connected electrically with the inside of the air conditioned environment, make holes for the passage of cables (one for the power cable, one for the user terminal connection and the control cables); 70 Ø 30 mm 264 502 367 Ø 30 mm 55 Ø 36 mm Ø 22 mm 57 40 40 92 45 575 785 105 45 85 WM*0121-0181 Fig. 13. WM*0251-0331 WM*0551-0661 7. Fix unit support bracket D with three screws E (see fig. 12. - 14.); n.
INSTALLATION Wall Mounted 0121…0661 CONNECTING THE CONDENSATE DRAIN The condensate tray is located at the base of the evaporate coil; the condensate drains from the tray via a flexible tube (included with the unit) behind the condensate coil.
INSTALLATION Wall Mounted 0121…0661 ELECTRICAL CONNECTIONS Correct and accurate electrical connections, carried out in compliance with local regulations, are extremely important for the prevention of accidents and for ensuring long, trouble-free operations.
INSTALLATION Wall Mounted 0121…0661 CONNECTING THE POWER SUPPLY CABLES - 0121-0331 MODELS: Locate the terminal blocks positioned to the left of the compressor; WM* 0121-0181-0251 L1 N PE UPS (Opt.) L10 N10 WM* 0331 L1 L2 L3 N PE UPS (Opt.) - L10 N10 Fig. 17.a. 0121-0331 MODELS: (special versions) on a few special unit versions the terminal block beside the compressor is non supplied and the power supply cables are therefore directly connected to the terminals of the mains switch.
INSTALLATION Wall Mounted 0121…0661 - 0551-0661 models: Locate the mains switch IG found inside the electrical circuit; UPS (Opt.) IG I O L10 N10 L1 L2 L3 N PE IM2 IM1 Fig. 17.c. - Fix the cable terminals to the mains switch and secure the screws; connection of the yellow/green earth wire using the terminal ‘PE’ is compulsory.
INSTALLATION Wall Mounted 0121…0661 RECOMMENDED POWER SUPPLY CABLE SECTIONS AND LINE FUSES Power cable is not supplied by UNIFLAIR ITALIA Srl and must be appropriately dimensioned by the installer. For short distances ( < 30 m ) the recommended sections are shown in the table below: MAIN 230V/1N/50Hz LINE MODEL LINE FUSE (a) UPS 230V/1N/50Hz LINE (opt.) MODEL LINE WM* 0121 2x4+4PE 40A WM* 0121 2x1.5 WM* 0181 2x4+4PE 40A WM* 0181 2x1.5 WM* 0251 2x4+4PE 40A WM* 0251 2x1.
INSTALLATION Wall Mounted 0121…0661 TEMPERATURE AND HUMIDITY SENSOR (optional) The optional temperature and humidity sensors ASXC must be installed as shown in the unit’s electrical diagrams. ASW 80 126 mm Fig. 20. Temperature setting is done on the user termianl (see MP20 instruction manual); adjustment is at intervals of 0.1°C; maximum adjustment is between –9.9°C and +9.9 °C. 20 (22) Monobloc Wall Mounted Unit - WMA/WMF 0121-0181-0251-0281-0331-0551-0661 - Rev. 2.0.
INSTALLATION Wall Mounted 0121…0661 Monobloc Wall Mounted Unit - WMA/WMF 0121-0181-0251-0281-0331-0551-0661 - Rev. 2.0.
INSTALLATION UNIFLAIR ITALIA S.r.l. Via dell’industria, 10 35020 BRUGINE (Padova) - Italy Tel. +39 (0)49 9713211 Fax +39 (0)49 5806906 22 (22) Internet: www.UNIFLAIR.com E-mail: INFO@UNIFLAIR.com Manual code @ digit: 06MM010 @ 00B0200 Wall Mounted 0121…0661 Monobloc Wall Mounted Unit - WMA/WMF 0121-0181-0251-0281-0331-0551-0661 - Rev. 2.0.