UPS313-01-00 MINIpower PLUS (Rack) User Manual, Dated 01-08-06 8-3
There is a danger of explosion should the batteries be replaced with
the wrong type.
Dispose of used batteries as per the instructions and precautions for
their disposal on the battery label.
Output When Running on Battery Power
Model 1250 2500 3750 5000
Nominal Output Voltage 230 V ± 1%
Nominal Output frequency 50 Hz / 60Hz synchronised (autosensing and/or as selected by operator)
Output VA 1250 2500 3750 5000
Output W
with 0.7 pf linear/non-linear load
875 1750 2625 3500
THD < 1%
Overload Capacity 160% for 15s
Allowable load pf 0.7-1.0
DC-AC conversion efficiency 80% with 50% linear load pf = 1 and charged batteries:
80% with 75% load
80% with 100% load
Battery Operation
Model 1250 2500 3750 5000
Approximate autonomy in minutes with charged batteries
Percentage of applied load 50 80 100 50 80 100 50 80 100 50 80 100
Standard UPS 20 11 8 20 11 8 20 11 8 20 11 8
Recharge time to 90% charge 5 - 6 hours according to level of discharge
Specifications and quantity of
batteries
3 pcs 12V 9Ah, sealed, lead-acid, maintenance free batteries connected in series for each
power module
Reserve signals 32.2 V to 36V, programmable
Minimum voltage for battery
operation during discharge
27V to 31.5V with automatic selection depending on applied load, or as programmed by
operator.
Average battery life 3-6 years according to use and working temperature
The UPS batteries are subject to a reduction in capacity depending on their age (a
feature declared by their manufacturer in the technical manual). For example, the
reduction of capacity of a 4-year-old battery can be as much as 40%, resulting in a
proportional reduction of UPS autonomy time when running on battery power.