R o Uninterruptible Power Supply nline UPS 1KVA ~ 3KVA R www.cbcinter.co.
TRUE ON LINE UPS 1. Introduction Contents 1. Introduction 1 2. Safety Instructions 2 3. Description of commonly used Notations 5 4. System Description 6 5. Connection and Operation 14 6. Trouble Shooting 21 7. Maintenance 23 This On-Line-Series is an uninterruptible power supply incorporating double-converter technology. It provides perfect protection specifically for Novell, Windows NT and UNIX servers. The double-converter principle eliminates all mains power disturbances.
TRUE ON LINE UPS 2. Safety Instructions PLEASE READ THE FOLLOWING USER MANUAL AND THE SAFETY INSTRUCTIONS BEFORE INSTALLING THE UNIT AND STARTING IT UP! 2-1 Transport Please transport the UPS system only in the original packaging (to protect against shock and impact). 2-2 Set-up Condensation may occur if the UPS system is moved directly from a cold to a warm environment. The UPS system must be absolutely dry before being installed. Please allow an acclimatization time of at least two hours.
TRUE ON LINE UPS For 6K / 10K models, the maintain switch, bypass switch and input switch are still electrically live and dangerous even after the input switch and bypass switch are disconnected on carrying out servicing and/or maintenance. Only persons that are adequately familiar with batteries and wi th the required precautionary measures may replace batteries and supervise operations. Unauthorised persons must be kept well away from the batteries. Caution - risk of electric shock.
TRUE ON LINE UPS TRUE ON LINE UPS 4. System Description Switch 3 Load/Battery Capacity LED 4 Load/Battery Capacity LED 2 Load/Battery Capacity LED ON - Switch 5 Load/Battery Capacity LED 6 Load/Battery Capacity LED 1 Fault LED 7 Bypass LED 8 Line LED 9 Inverter LED 10 Battery LED ON-Switch/Alarm Silence OFF-Switch Figure 1: LED Display Panel 1 OFF-Switch Display 6 Load/Battery Capacity LED 5 Load/Battery Capacity LED LINE LED 4 Load/Battery Capacity LED 1 Fault LED Function 1.
TRUE ON LINE UPS TRUE ON LINE UPS LCD display content and relative work model LCD Display Screen Main power in or first time UPS ON LCD display: Bypass LED Line LED Inverter LED WELCOME TO USE ONLINE UPS Fault LED Battery LED ON-Switch/Alarm Silence OFF-Switch Display Cycle Button UPS work at bypass model, press the LCD will display as follows: Display cycle button on front panel, Figure 4: LCD Display Panel 1 SYSTEM NORMAL BYPASS OUPRUT LCD Display Screen Line LED Bypass LED BYPASS UPS work at i
TRUE ON LINE UPS TRUE ON LINE UPS Press the Display cycle button as follows: on front panel once more, LCD will display Press the Display cycle button as follows: INPUT FREQUENCY 50.0HZ Here display the input main power frequency parameter, this numerical value can inspect main power frequency variety, from 0HZ~60HZ. Press the Display cycle button as follows: Here display the UPS output voltage parameter, this numerical value can inspect UPS output voltage variety, from 0V~290V.
TRUE ON LINE UPS TRUE ON LINE UPS Communication Interface Communication Interface Fan Input Switch Intelligent Slot Battery Connector(H Model) Fan Battery Connector(H Model) Intelligent Slot Terminal Block Breaker Network/Fax/Modem Surge Protection 6KR Rear Panel Output Socket Communication Interface Input Socket Intelligent Slot Fan 1KL Rear Panel Parallel Card Port(Option) Communication Interface Battery Connector(H Model) Intelligent Slot Input Switch Service Bypass(Option) Battery
TRUE ON LINE UPS TRUE ON LINE UPS 5. Connection and Operation THE SYSTEM MAY BE INSTALLED AND WIRED ONLY BY QUALIFIED ELECTRICIANS IN ACCORDANCE WITH APPLICABLE SAFETY REGULATIONS! 5.1 Connection and operation for 1K / 2K / 3K WHEN INSTALLING THE ELECTRICAL WIRING, PLEASE NOTE THE NOMINAL AMPERAGE OF YOUR INCOMING FEEDER. 1/2/3KVA UPS Input connection 1KVAH External Battery Connection 2/3KVAH External Battery Connection 1) Inspection: Inspect the packaging carton and its contents for damage.
TRUE ON LINE UPS 2) Connection: 2-1) UPS Input Connection If the UPS is connected via the power cord, please use a proper socket with protection against electric current, and pay attention to the capacity of the socket: over 10A for 1KS(H) & 2K, over 16A for 2KH & 3KS(H). 2-2) UPS Output Connection The output of 1KS(H),2KS(H) and 3KS(H) are socket-types only. Simply plug the load power cord to the output sockets to complete connection.
TRUE ON LINE UPS TRUE ON LINE UPS (2) One end of the external battery cord is a plug for connecting the UPS and the other end has 3 (or 2) open wires for connecting the battery pack. The battery connection procedure is very important. Any incompliance may result in the risk of electric shock. Therefore, the following steps must be strictly complied with. (3) First connect in series the batteries of the pack to ensure proper battery voltage.
TRUE ON LINE UPS 5) Battery Charge: Fully charge the batteries of the UPS system by leaving the UPS system connected to the mains for 8-10 hours. You can also use the UPS system directly without charging it but the stored energy time may then be shorter than the nominal value specified. 6) Turn On the UPS: 6-1) With utility power connecting: Press I button continuously for more than 1 second and set the Breaker on the rear panel to the ON position to turn on the UPS.
TRUE ON LINE UPS Problem No indication, no warning tone even though system is connected to mains power supply TRUE ON LINE UPS Possible cause Please have the following information at hand before calling the After-Sales Service Department: 1. Model number, serial number 2. Date on which the problem occurred 3. Detailed description of the problem Remedy No input voltage Check building wiring socket outlet and input cable.
TRUE ON LINE UPS TRUE ON LINE UPS 8.3 Typical stored energy time (Typical values at 25 minutes:) 8. Technical data 8.1 Electrical specifications INPUT Model No. 1K Voltage 6K 10K 176~276VAC 115~300VAC Frequency Current(A) 3K 2K (46~54)Hz /(56~64)Hz 7A 12A 16A 30A 47A 1K 2K 3K 6K 10K OUTPUT Model No. Power rating Voltage Frequency Model No. 100 % Load 50 % Load 1K 5 14 2K 9 21 3K 5 15 6K 8 23 10K 5 12 8.4 Dimensions and weights 1kVA/0.7kW 2kVA/1.4kW 3kVA/2.
TRUE ON LINE UPS Harmonic Current: EN61000-3-2 Voltage Fluctuations and Flicker: EN61000-3-3 EMS: EN61000-4-2(ESD).......................................................Level 4 EN61000-4-3(RS) ....................................................................Level 3 EN61000-4-4(EFT)...................................................................Level 4 EN61000-4-5(lighting surge)...................................................
TRUE ON LINE UPS TRUE ON LINE UPS APPENDIX APPENDIX : Front panel LED display and Work Model parallelism diagram 1KVA, 2KVA and 3KVA: LED No Work Model No 0 ~35 Load Capacity 1 3 Main Power Alarm Beep No No 1 0%~35% Load Capacity No 2 36%~55% Load Capacity No 3 Main 56%~75% Load Capacity Power No No No 56 ~75 Load Capacity LED No Alarm Beep No 36 ~55 Load Capacity 2 6KVA and 10KVA: Work Model 4 76 ~95 Load Capacity No 4 76%~95% Load Capacity 96 ~105 Load Capacity No 5 9
TRUE ON LINE UPS TRUE ON LINE UPS APPENDIX : Parallel operation (6KVA and 10KVA) Input Switch Board 1. Brief introduction of the redundancy N+X is currently the most reliable power supply structure. N represents the minimum UPS number that the total load needs; X represents the redundant UPS number, i.e. The fault UPS number that the system can handle simultaneously. The bigger the X is, the higher reliability of the power system is.
UPS1 O/P Wiring Breaker UPS1 O/P Wiring Breaker 32 UPS2 O/P Wiring Breaker UPS2 O/P Wiring Breaker TRUE ON LINE UPS Parallel Installation Diagram I/P CHD I/P N I/P L I/P L I/P N I/P CHD