3.7.3. Door
Select [ENT~] [5. Terminal] [3. Door] in the initial screen , and the following
screen appears:
Initial setting: Identical with the screen on the left.
Lock Type
Set to ‘1’ when strike type or automatic door is connected to the terminal, or 2’ when
motorized lock is connected to the terminal. If no connection is made, it is set to ‘1’.
Set to ‘3’ when connecting a warning lamp to the lock port to indicate the success or
failure of authentication.
DM1: To connect an external contact to DM1 (Set 1 or 2 for motor locks)
- 0. Not in use’: none in connection
- 1. Door open NO’ or ‘2. Door open NC’: A door status monitoring pin in connection
- 3. Fire detection NO’ or ‘4. Fire detection NC’: A fire sensor in connection
- ‘5. Panic detection NO’ or 6. Panic detection NC’: A panic situation sensor in
connection
- 7. Emergency detection NO’ or 8. Emergency detection NC’: An emergency situation
sensor in connection
Configure NO/NC depending on the pin status upon detection
- ‘9. Controller authorization result’: It sends the authorization result to the external
controller.
(You should connect the RED led of the controller with DM1 or DM2 through the board toward TR, and
the pin should be set 9. Controller result. You should set the Wiegand Out.)
DM2: To connect an external contact to DM2 (Set 1 or 2 for motor locks)
- 0. Not in use’: none in connection
- 1. Lock status NO’ or ‘2. Lock status NC’: A lock status monitoring pin in connection
- 3. Fire detection NO’ or ‘4. Fire detection NC’: A fire sensor in connection
- 5. Panic detection NO’ or 6. Panic detection NC’: A panic situation sensor in
connection
- 7. Emergency detection NO’ or 8. Emergency detection NC’: An emergency situation
sensor in connection
Configure NO/NC depending on the pin status upon detection
- ‘9. Controller authorization result’: It sends the authorization result to the external
controller.
(You should connect the RED led of the controller with DM1 or DM2 through the board toward TR, and the
pin should be set 9. Controller result. You should set the Wiegand Out.)