OPERATING MANUAL INVO Series 5KVA INVERTER / CHARGER INVC4850H – 48V Battery INVC9650H – 96V Battery WWW.UNIPOWERCORP.COM Manual No. INVO-1 © 2011 UNIPOWER Corp. All Rights Reserved 08/11 invo-.man UNIPOWER Corporation NORTH AMERICA • 3900 Coral Ridge Drive, Coral Springs, Florida 33065, USA • Tel: +1 954-346-2442 • Fax: +1 954-340-7901 • sales@unipower-corp.
INVO SERIES INVERTER/CHARGER INSTALLATION & OPERATING MANUAL Manual No.
INVO SERIES INVERTER/CHARGER INSTALLATION & OPERATING MANUAL Contents ABOUT THIS MANUAL ...............................................................................................................4 Purpose .................................................................................................................................................. 4 Scope ...................................................................................................................................................
INVO SERIES INVERTER/CHARGER INSTALLATION & OPERATING MANUAL ABOUT THIS MANUAL Purpose The purpose of this manual is to provide explanations and procedures for installation, operation and troubleshooting. This manual should be read carefully before installation and operation. Please retain this manual for future reference. Scope This document defines the functional requirements of the inverter/charger, which is intended for worldwide use in electronic data processing applications.
INVO SERIES INVERTER/CHARGER INSTALLATION & OPERATING MANUAL 8. No terminals or lugs are required for hook-up of the AC wiring. AC wiring must be no less than 10 AWG gauge copper wire and rated for 75oC or higher. Battery cables must be rated for 75oC or higher and should be no less than as stated in table 1. Crimped and sealed copper ring terminal lugs with a 5/16 hole should be used to connect the battery cables to the DC terminals of the inverter/charger. Soldered cable lugs are also acceptable. 9.
INVO SERIES INVERTER/CHARGER INSTALLATION & OPERATING MANUAL INSTALLATION Unpacking and Inspection Carefully unpack the inverter/charger from its shipping carton. Verify all of the items listed below are present. Please call customer service if any items are missing: The Inverter/Charger 1 DC red cable 1 DC black cable 1 User’s manual (this document) Basic Configuration The following illustration shows the basic utility backup application for the Invo Series 5KVa inverter/charger.
INVO SERIES INVERTER/CHARGER INSTALLATION & OPERATING MANUAL The Invo Series 5KVA Inverter/Charger can feed almost any kind of appliance including those with motor characteristic, e.g. fluorescent lights, fans, refrigerators and air conditioners. Note: Appliances such as air conditioners often require at least 3 minutes to restart after a short-term power outage (time is required to balance the refrigerant gas in inside circuit).
INVO SERIES INVERTER/CHARGER INSTALLATION & OPERATING MANUAL DC Disconnect and Over-Current Protection For safety and to comply with regulations, battery over-current protection and disconnect devices are required. Fuses and disconnects must be sized to protect the DC cable size used, and must be rated for DC operation. Do not use devices rated only for AC service – they will not function properly.
INVO SERIES INVERTER/CHARGER INSTALLATION & OPERATING MANUAL AC Cable Size Before wiring the input and output of the inverter, refer to table 2 for minimum recommended cable sizes and torque values. Model Number AC Input AC Output Torque value INVC5048H 10AWG 10AWG 1.2~1.8 Nm INVC5096H 10AWG 10AWG 1.2~1.8 Nm Table 2 - Min recommended cable size, torque value for AC wiring AC Connections Installation should be done only by a qualified electrician.
INVO SERIES INVERTER/CHARGER INSTALLATION & OPERATING MANUAL 4. Connect the AC Line output wiring to the terminal marked AC Line (output) following the wiring guide inside the compartment. Connect the AC neutral out to the AC neutral out terminal. Torque the wires into the terminal block. 5. Use the two M3 screws to lock the AC cover. 6. Tighten the clamps on the AC cable jackets (not the individual wires) to provide strain relief for the connections. Manual No.
INVO SERIES INVERTER/CHARGER INSTALLATION & OPERATING MANUAL OPERATION Front Panel Controls and LCD Indicators Figure 5 shows the controls and indicator lights on the front of the INVO Series inverter/charger. They control and provide information in both inverter and battery charging modes of operation. LCD indicator On/Off switch Configuration switches Figure 5 - Front Panel Power ON/OFF Located on the left of the panel is the ON/OFF Switch.
INVO SERIES INVERTER/CHARGER INSTALLATION & OPERATING MANUAL LCD Indicator The LCD display provides system status, and the user-friendly panel eases program settings. See Figure 6. Figure 6 - LCD display interface AC Mode Indicator The line mode symbol will show and the indicator will display the input voltage, output voltage and load. Inverter Mode Indicator The inverter mode symbol will show and the indicator will display the input voltage, output voltage, load.
INVO SERIES INVERTER/CHARGER INSTALLATION & OPERATING MANUAL Load indicator The load indicator shows the load percentage in VA or W, whichever is bigger, the overload indicator will flash when an overload is present. Battery Charger Inverter to Charger Transition The internal battery charger and automatic transfer relay allow the inverter/charger to operate as either a battery charger or an inverter (but not both at the same time).
INVO SERIES INVERTER/CHARGER INSTALLATION & OPERATING MANUAL SPECIFICATIONS Table 5 - Line Mode Specifications MODEL INVC5048H Input Voltage Waveform INVC5096H Sinusoidal (Utility or Generator) Nominal Input Voltage High Line Disconnect 230Vac 170Vac (Normal) 90Vac (Generator / Wide Range) 180Vac (Normal) 100Vac (Generator / Wide Range) 280Vac High Line Re-connect 270Vac Max AC Input Voltage 300Vac rms Low Line Disconnect Low Line Reconnect Nominal Input Frequency 50Hz / 60Hz (Auto-detect)
INVO SERIES INVERTER/CHARGER INSTALLATION & OPERATING MANUAL Table 6 - Inverter Mode Specifications MODEL INVC5048H Output Voltage Waveform INVC5096H Pure Sine Wave Rated Output Power 5,000VA Power Factor 0.
INVO SERIES INVERTER/CHARGER INSTALLATION & OPERATING MANUAL Table 7 - Charge Mode Specifications MODEL Nominal Input Voltage Input Voltage Range Nominal Output Voltage Nominal Charge Current Battery initial voltage(sps setup) Charger Short Circuit Protection Over Charge Protection Charge Algorithm Battery Type Setting(±0.3V/batt.
INVO SERIES INVERTER/CHARGER INSTALLATION & OPERATING MANUAL Table 8 - General Specifications Safety Certification CE(EN60950) EMI Classification EN62040-2, CLASS A Operating Temperature Range 0°C to 45°C Storage temperature -15°C ~ 60°C Altitude, operational Elevation: 0 ~ 1500 Meters Relative humidity 5% to 95% non-condensing Audible Noise 60dB max.
INVO SERIES INVERTER/CHARGER INSTALLATION & OPERATING MANUAL TROUBLESHOOTING Problem No LCD display Possible Causes 1. Battery Weak <35V for 5048H <70V for 5096H 2. Battery defective (can't be charged) Remedy 1. Re-charge battery 2. Replace Battery 3. Power switch is not pressed Mains normal but operates in inverter mode 4. Battery polarity reversed Can’t start up the inverter/charger 1. AC input missing 2. Input breaker triggered 1. Overload 2. Output short circuit 3. Over temp 4.