User's Manual

Chapter 6 Maintenance
6.5.6.2 Air-to-Air Heat Exchanger/Heater Installation
T
he replacement air-to-air heat exchanger/heater should be installed in HB cabinet or LB
cabinet in the following sequence:
1. Before the replacement air-to-air heat exchanger/heater is installed, ensure that the
weatherproof gasket is placed on the side of the air-to-air heat exchanger/heater that
will rest against the side of the cabinet – see Figure 6-11
.
2. Using two handlers, one located on each side of the air-to-air heat exchanger/heater,
carefully lift the air-to-air heat exchanger/heater and place it in the opening in the
side of the cabinet.
3. Replace the twelve (12) 1/4-20 socket head cap screws (with 1/4” flat washers and
gaskets) which secure the air-to-air heat exchanger/heater to the cabinet – see Figure
6-10
. A torque rating of 45.6 Inch Lbs. must be used to tighten the screws.
4. Install four (4) cable tie mounts on the air-to-air heat exchanger/heater inside panel
– see Figure 6-9
.
5. Secure the two (2) temperature sensor cable assemblies (ELECTR COMP AIR INTAKE
and ELECTR COMP AIR EXH) to the cable tie mounts located on the air-to-air heat
exchanger/heater inside panel – see Figure 6-9
.
6. Re-connect the 8-pin pluggable terminal block to the air-to-air heat exchanger/heater
inside panel 8-pin terminal block receptacle – see Figure 6-9
.
7. Switch ON the HE circuit breaker (CB 5), located on the HB cabinet PDU or LB cabinet
PDU.
8. Close the electronics compartment front and rear doors.
SX03-2000
0-01-M01 6-25