User's Manual

Table Of Contents
Page 33
X75 SERIES
INSTALLATION & OPERATING MANUAL
Manual No. x75-10b
x75-man-Rev10b-0514.indd
SITE DETAILS
Site Name – Optional setting which may be used to identify the location of the unit.
Serial Number – Displays the unit serial number. (Cannot be changed.)
SYSTEM VOLTAGES
System – Dial in the Nominal system voltage; 12V, 24V or 48V.
Float – Enter the oat voltage in accordance with the specications of the batteries
that are being employed with the system.
Equalize Enter the equalization voltage in accordance with the specications of
the batteries that are being employed with the system.
Equ Time – Enter the desired time that the system should remain in equalize mode
in accordance with the specications of the batteries that are being employed with
the system.
SYSTEM SHUNTS
Rect Shunt Amps – This is the 50mV Full-Scale rating for the internal shunt that
is used to measure the total rectier current. THIS SETTING SHOULD NOT BE
CHANGED.
Load Shunt Amps – This is the 50mV Full-Scale rating for the shunt that is used to
measure the total load current. THIS SETTING SHOULD NOT BE CHANGED.
LVD SETTINGS
LVD1 Off – Enter the voltage at which the LVD1 contactor will open during a
battery discharge. The factory default setting is that recommended for most sealed
lead acid batteries.
LVD1 On – Enter the voltage at which the LVD1 contactor will re-connect once
the rectiers are running. The factory default setting is that recommended for most
sealed lead acid batteries.
LVD2 Off & LVD2 On – These settings are not required for the X75.