User's Manual Part 1

Chapter 3 Installation
The following steps should be performed to make the electrical connection to the repeater
PDU once the power cable has been routed into the cabinet and prepped by a certified
electrician:
Place the circuit breaker in the building/site electrical service panel in the
OFF position and place a “DANGER-DO NOT TURN ON - Personnel
Working” sign on the circuit breaker.
1. Remove the terminal block access panel from the back of the PDU by removing the
four (4) Phillips head screws – see Figure 3-39
.
2. Insert the green wire into the terminal block marked “GND” and tighten the clamping
screw – see Figure 3-40
.
3. Insert the white wire into the terminal block marked “N” and tighten the clamping
screw – see Figure 3-40
.
4. Insert the red wire into the terminal block marked “L2” and tighten the clamping screw
– see Figure 3-40
.
5. Insert the black wire into the terminal block marked “L1” and tighten the clamping
screw – see Figure 3-40
.
6. Replace the PDU terminal block access panel and verify that all PDU breakers are in
the OFF position.
7. Verify that the circuit breaker in the building/site electrical service panel is still in the
OFF position and that the AC disconnect device is in the OFF position (where
applicable).
8. Place the circuit breaker in the building/site electrical service panel in the ON position
and remove the sign.
9. Place the AC disconnect device in the ON position (where applicable).
SX03-10000-01-M01 3-48