Chapter 3 Installation
3.15.2 Repeater Cabinet Ground Connection
The repeater cabinets must be connected to the building/site’s main
ground terminal.
An external ground conductor can be secured to the ground stud located on the floor of the
control cabinet, near the back right corner – see Figure 3-55
. A torque rating of 45 – 50 In.
Lbs. should be used to tighten the nut.
An external ground conductor can be secured to the ground stud located on the floor of the
HB HPA cabinet, near the back right corner – see Figure 3-56
. A torque rating of 45 – 50 In.
Lbs. should be used to tighten the nut.
An external ground conductor can be secured to the ground stud located on the floor of the LB
HPA cabinet, near the back left corner – see Figure 3-57
. A torque rating of 45 – 50 In. Lbs.
should be used to tighten the nut.