User Manual

IMPORTANCE OF LEVELING A REFRIGERATOR
The refrigerator must be adjusted to a vertical position in both directions. In an absorption refrigeration
system, ammonia is liquefied in the finned condenser coil at the top rear of the refrigerator. The liquid
ammonia then flows into the evaporator (inside the freezer section) and is exposed to circulating flow of
hydrogen gas, which causes the ammonia to evaporate, creating a cold condition in the freezer.
When starting this refrigerator for the very first time, the cooling cycle may require up to 8 hours of running
time before the cooling unit is fully operational to begin slowly loading compartment with cold food from
your cooler.
At room temperatures under 60°F (15.5°C), there is a risk that the temperature in the main compartment
will drop below freezing point, even with the thermostat at the warmest setting. Optimal operating
temperatures shall be between 65°F (18°C) and 9F (32°C). Storage and non-operating temperatures
can be between 5°F (-15°C) and 104°F (40°C). The fridge must always be brought up to average room
temperature before starting e.g. 65°F (18°C).
The tubing in the evaporator section is specifically sloped to provide a continuous movement of liquid
ammonia, flowing downward by gravity through this section. If the refrigerator is operated when not
level, liquid ammonia will accumulate in sections of the evaporator tubing. This will slow the circulation of
hydrogen and ammonia gas, or in severe cases, completely block it, resulting in a loss of cooling. Warranty
will not cover recharge/rebuild if caused by not running the fridge level.
THIS REFRIGERATOR OPERATES ON LP GAS (PROPANE) & 110V (ELECTRICITY)
Note: After changing an LP tank, or after a long shut off period, the gas line is likely to be filled with air. You
may have to repeat the lighting procedure several times to purge the air out of the gas lines. We suggest
first turning off gas at the control panel, then the tank, this will reduce an air trap in the gas line.
GAS OPERATION – FOR MODELS WITH ELECTRONIC IGNITION
“START-UP” PROCEDURE
Electronic Ignition (battery)
1. To start the refrigerator, turn the thermostat knob E to the maximum setting, #4.
2. Turn button G to “Gas” position, then push B button in first and hold, proceed to push in and hold the D
button until you see the needle on the flame sensor C moving from the red into the green area. Release
the B button, while continuing to hold in the D button for an additional 10-15 seconds, now release the D
button. The burner should now stay on indicated by the needle staying in the green area, if not repeat the
lighting instructions above.
3. Adjust the thermostat knob E to desired temperature setting after 8 or more hours of operation.
4. To change the battery in the electronic ignition, turn the far left knob A to the left to expose the battery,
remove AAA battery and replace with a new one, positive outwards, replace the knob by turning to the
right to close.
SHUT DOWN PROCEDURE – GAS OPERATION
1. Turn selector knob G to the OFF position
2. Shut the gas o at the LP-gas supply cylinder when the appliance is not in use.
3. If the refrigerator will not be in operation for a period of weeks, it should be emptied, defrosted, cleaned
and the door left open.
8
GENERAL OPERATING INSTRUCTIONS