SM SOLAR MOUNT TABLE OF CONTENTS A - SYSTEM COMPONENTS B - SYSTEM LAYOUT C - CODE COMPLIANCE NOTES D - ROOF ATTACHMENT & L-FEET E - SPLICE & THERMAL BREAK F - ATTACH RAIL TO L-FEET G - MICROINVERTER MOUNTING H - MICROINVERTER SYSTEM GROUNDING I - GROUNDING, MICROINVERTER W/THERMAL BREAK J - STANDARD SYSTEM GROUNDING K - END CLAMP, FIRST MODULE L - BONDING MID CLAMP M - REMAINING MODULES N - TRIM INSTALLATION O - BONDING CONNECTION GROUND PATHS P - TEMPORARY BONDING AND ELECTRICAL NOTES APPENDIX A : SYSTEM
SM STANDARD SYSTEM COMPONENTS SOLAR MOUNT INSTALLATION GUIDE PAGE RAIL: Supports PV modules. Use at least two per A SM STANDARD RAIL SM LIGHT RAIL Wrenches and Torque Anti-Seize Wrench or Socket Size Recommended Torque (ft-lbs) Mid Clamp 1/2” 11 MLPE Mount 1/2” 10 End Clamp 1/2” 3 L-Foot to Rail 1/2” 30 Rail Splice 1/2” 10 Stainless steel hardware can seize up, a process called galling. To significantly reduce its likelihood: 1.
SM SYSTEM LAYOUT SOLAR MOUNT B INSTALLATION GUIDE PAGE PLANNING YOUR SOLARMOUNT INSTALLATIONS The installation can be laid out with rails parallel to the rafters or perpendicular to the rafters. Note that SOLARMOUNT rails make excellent straight edges for doing layouts.
SM SOLAR MOUNT CODE COMPLIANCE NOTES C INSTALLATION GUIDE PAGE SYSTEM LEVEL FIRE CLASSIFICATION The system fire class rating requires installation in the manner specified in the SOLARMOUNT Installation Guide. SOLARMOUNT has been classified to the system level fire portion of UL 1703. This UL 1703 classification has been incorporated into our UL 2703 product certification. SOLARMOUNT has achieved system level performance for steep sloped roofs.
SM SOLAR MOUNT ROOF ATTACHMENT & L-FEET D INSTALLATION GUIDE PAGE ROOF PREPARATION: Layout and install flashing at rafter locations determined per Design and Engineering Guide. DRILL PILOT HOLES: Center the roof attachment over the rafter and drill a pilot hole(s) for the lag bolt(s). NOTE: Determine lag bolt size and embedment depth. FLASHING INSTALLATION: Insert the flashing so the top part is under the next row of shingles and the hole lines up with the pilot hole.
” /16 o3 0t E INSTALLATION GUIDE PAGE SM SPLICE & THERMAL BREAK SOLAR MOUNT p ga b n ee etw ls rai SPLICE INSTALLATION (IF REQUIRED PER SYSTEM DESIGN) If your installation uses SOLARMOUNT splice bars, attach the rails together before mounting to the L-feet / footings. Use splice bars only with flush installations or those that use low-profile tilt legs. A rail can be supported by more than one footing on both sides of the splice.
SM ATTACH RAIL TO L-FEET SOLAR MOUNT INSTALLATION GUIDE PAGE 3/8” T-bolt PLACE T-BOLT INTO RAIL & SECURE BOLT: Insert 3/8” T-bolt into rail at L-foot locations. Apply Anti-Seize to bolt. Rotate T-bolt into position. SECURE T-BOLT: Apply Anti-Seize to bolt. Rotate T-bolt into position. ALIGN POSITION INDICATOR: Hand tighten nut until rail alignment is complete. Verify that position indicator on bolt is vertical (perpendicular to rail) TORQUE VALUE (See Note on PG.
SM MICROINVERTER MOUNTING SOLAR MOUNT INSTALLATION GUIDE PAGE INSTALL MICROINVERTER MOUNT T-BOLT: Apply Anti-Seize and install pre-assembled ¼” dia. bonding T-bolts into top ¼” rail slot at microinverter locations. Rotate bolts into position. G INSTALL MICROINVERTER: Install microinverter on to rail. Engage with bolt. INSTALL MICROINVERTER: TORQUE VALUE (See Note on PG.
SM SOLAR MOUNT MICROINVERTER SYSTEM GROUNDING H INSTALLATION GUIDE PAGE SM EQUIPMENT GROUNDING THROUGH ENPHASE MICROINVERTERS The Enphase M215 and M250 microinverters have integrated grounding capabilities built in. In this case, the DC circuit is isolated from the AC circuit, and the AC equipment grounding conductor (EGC) is built into the Enphase Engage integrated grounding (IG) cabling.
SM ELECTRICAL GROUNDING W/ SOLAR ENPHASE I MICROINVERTER FOR SPLICE & THERMAL BREAK INSTALLATION GUIDE PAGE MOUNT CONTINUOUS RAIL & ELECTRICAL BONDING SPLICE EXPANSION JOINT W/GROUNDING LUGS & COPPER JUMPER EXPANSION JOINT W/O ELECTRICAL BONDING CONNECTION Enphase Microinverter (MI) Requirements (Model No. M215 & M250) Enphase Microinverter (MI) Requirements (Model No. M215 & M250) Enphase Microinverter (MI) Requirements (Model No.
WEEBLUG Single Use Only ONLY ONE LUG PER ROW OF MODULES: Only one lug per row of modules is required. See Page F for additional lugs required for expansion joints. GROUNDING LUG - BOLT SIZE & DRILL SIZE BOLT SIZE DRILL SIZE WEEBLug 1/4" N/A - Place in Top SM Rail Slot IlSCO Lug #10-32 7/32" • • Torque value depends on conductor size. See product data sheet for torque value.
SM ENDCLAMP, FIRST MODULE &TRIM SOLAR MOUNT INSTALLATION GUIDE PAGE INSTALL MODULE END CLAMPS: The End clamp is supplied as an assembly with a 1/2" hex head bolt that is accessible at the ends of rails. The clamp should be installed on the rails prior to installing end modules. INSTALL END CLAMPS ON RAIL: Slide end clamp on to rail by engaging the two t-guide brackets with the top slot of the rails. Ensure bolt is extended as far as possible so that clamp is positioned at max.
INSTALL MIDCLAMPS: Midclamp is supplied as an assembly with a T-bolt for module installation. Clamp assemblies may be positioned in rail near point of use prior to module placement. INSERT MIDCLAMP ASSEMBLY: Insert 1/4" T-Bolt into top slot of rail PLACE ADJACENT MODULE AGAINST CLAMPS: Modules must be tight against clamps with no gaps. Tighten nut to required torque. POSITION INDICATOR - SERRATED T-BOLT: Verify the T-bolt position indicator is perpendicular to the rail.
SM REMAINING MODULES SOLAR MOUNT INSTALLATION GUIDE PAGE INSTALL REMAINING MID-CLAMPS: Proceed with module installation. Engage each module with previously positioned Midclamp assemblies. POSITION T-BOLT ALIGNMENT MARKS: Verify that the position indicator(s) & T-bolt shaft(s) are angled in the correct position. Tighten to final torque. TORQUE VALUE (See table and notes on PG. A) 11 ft-lbs. No anti-seize.
SM SOLAR MOUNT TRIM AND END CAP INSTALLATION N INSTALLATION GUIDE PAGE Break line and discard top piece for SM Light Rail TRIM MIDCLAMPS: Ensure Trim lip is in contact with module face and verify alignment marks on T-bolts are in proper position, tighten midclamp on Trim, repeat at each gap between modules. TORQUE VALUE (See table and notes on PG. 1) 11 ft-lbs. No anti-seize. INSTALL END CAPS: End caps install as supplied on SM standard rail and SM light rail.
DU LE FR AM LE FR AM 1 E SM RAIL R ING 3 3 T-B O LIC LT BONDING MIDCLAMP ASSEMBLY BONDING MIDCLAMP ASSEMBLY 1 Aluminum mid clamp with stainless steel bonding pins that pierce module frame anodization to bond module to module through clamp 2 Stainless steel nut bonds aluminum clamp to stainless steel T-bolt 3 Serrated T-bolt head penetrates rail anodization to bond T-bolt, nut, clamp, and modules to SM rail D D E Option 1: Ground Through Enphase Trunk Cable B Option 2: Ground Lug w
SM SOLAR MOUNT TEMPORARY BONDING CONNECTION BONDING CONNECTION GROUND PATHS P INSTALLATION GUIDE PAGE REQUIRED ONLY FOR TEMPORARY BONDING DURNING ARRAY MAINTENANCE MODULE REMOVED BONDING MID CLAMPS MAINTAIN GROUND PATH co co Ils SO LI D PP CO ER W I RE Ils 4 B- SG 4 B- SG TEMPORARY BONDING CONNECTION DURING ARRAY MAINTENANCE When removing modules for replacement or system maintenance, any module left in place that is secured with a bonding Midclamp will be properly grounded.
SM APPENDIX A SOLAR MOUNT Q System Certification PAGE The SOLARMOUNT system has been certified and listed to the UL 2703 standard (Rack Mounting Systems and Clamping Devices for Flat-Plate Photovoltaic Modules and Panels). This standard included electrical grounding, electrical bonding, mechanical load and fire resistance testing. In conducting these tests, specific modules are selected for their physical properties so that the certifications can be broadly applied.
SM APPENDIX A SOLAR MOUNT R System Certification PAGE Electrical Bonding and Grounding Test Modules The list below is not exhaustive of compliant modules but shows those that have been evaluated and found to be electrically compatible with the SOLARMOUNT system.
SM APPENDIX A SOLAR MOUNT System Certification PAGE Electrical Bonding and Grounding Test Modules The list below is not exhaustive of compliant modules but shows those that have been evaluated and found to be electrically compatible with the SOLARMOUNT system. Manufacturer Q-Cells Q-Cells S Series/Model Q.PEAK-G3.1 XXX, Q.PEAK BLK-G3.1 XXX, Q.PLUS BFR G3.1 XXX, Q.PLUS-G3 XXX, Q.PRO G3 XXX, Q.PRO BFR-G3 XXX, Q.PEAK-G3 XXX, Q.PEAK BLK-G3 XXX, Q.PLUS BFR G4.1 XXX, Q.PRO BFR G4 XXX, Q.PRO BFR G4.
FLASH FLASHKIT KIT PRO PRO SM INSTALLATION GUIDE INSTALLATION GUIDE SOLAR MOUNT APPENDIX B F L A S H K I T P R O I S T H E C O M P L E T E F L A S H I N G A N D AT TA C H M E N T S O L U T I O N F O R C O M P O S I T I O N R O O F S . F L A S H K I T P R O I S T H E C O M P L E T E F L A S H I N G A N D AT TA C H M E N T S O L U T I O N F O R C O M P O S I T I O N R O O F S .