Datasheet

STRING LINE
ROOF PANEL SEAM
(SEAM CONFIGURATION MAY VARY)
SILVER BULLETâ„¢
SET SCREW
STANDING SEAM POWER CLAMP
(MAY VARY DEPENDING ON
PROFILE OF METAL ROOF PANEL)
DRAWN BY:
DATE:
SCALE:
1
STANDING SEAM POWER
CLAMP
4
PLACE THE L-FOOT AND INSERT THE STAINLESS STEEL SCREW INTO THE THE TOP OF THE
STANDING SEAM POWER CLAMP AND TORQUE WITH A CALIBRATED TORQUE WRENCH TO A
MINIMUM OF100 IN/LBS.
1
RJH
02/8/18
N.T.S.
2
3
MEASURE THE DISTANCE FROM THE EAVE TO THE FIRST ROW OF STANDING SEAM CLAMPS
AND USE A STRING LINE OVER THE ROOF PANEL SEAMS TO ESTABLISH A STRAIGHT
GUIDELINE FOR INSTALLATION.
ALIGN THE STANDING SEAM POWER CLAMP ON THE SEAM AS SHOWN IN THE ORIENTATION
BELOW, DEPENDING ON THE APPLICABLE SEAM PROFILE. SET THE SET SCREW(S) LOCATED
AT THE BOTTOM OF THE CLAMP. THE TORQUE SHOULD BE VERIFIED WITH A CALIBRATED
TORQUE WRENCH WITHIN THE RECOMMENDED GUIDELINES SET FORTH BELOW.
CONTACT UNIRAC, INC. FOR THE RECOMMENDED TORQUE REQUIREMENTS OF ANY METAL GAUGE AND/OR MATERIAL NOT
LISTED BELOW.
24 Ga. STEEL = 150 IN/LBS - 160 IN/LBS B. 22 Ga. STEEL = 180 IN/LBS - 200 IN/LBS
SOLARMOUNT INSTALLATION GUIDE FOR STANDING SEAM CLAMPS
L-FOOT
M8 x 1.25 STAINLESS
STEEL SCREW
1411 BROADWAY BLVD. NE - ALBUQUERQUE, NM 87102
PHONE: 505.242.6411 WEBSITE: UNIRAC.COM
004130M
STANDING SEAM CLAMP, MINI 1SS
004131M
STANDING SEAM CLAMP, STND 2SS
004132M
STANDING SEAM CLAMP, WIDE 2SS