Installation manual
66832-UIM-D-1205
14 Unitary Products Group
SUPPLY VOLTAGE CONNECTIONS
1. Provide a power supply separate from all other circuits. Install
overcurrent protection and disconnect switch per local/national
electrical codes. The switch should be close to the unit for conve-
nience in servicing. With the disconnect or fused switch in the OFF
position, check all wiring against the unit wiring label. Refer to the
wiring diagram in this instruction.
2. Remove the screws retaining the wiring box cover. Route the
power wiring through the opening in the unit into the junction box
with a conduit connector or other proper connection. In the junc-
tion box there will be three wires, a Black Wire, a White Wire and a
Green Wire. Connect the power supply as shown on the unit-wir-
ing label on the inside of the blower compartment door or the wir-
ing schematic in this section. The black furnace lead must be
connected to the L1 (hot) wire from the power supply. The white
furnace lead must be connected to neutral. Connect the green fur-
nace lead (equipment ground) to the power supply ground. An
alternate wiring method is to use a field provided 2” (51 mm) x 4”
(102 mm) box and cover on the outside of the furnace. Route the
furnace leads into the box using a protective bushing where the
wires pass through the furnace panel. After making the wiring con-
nections replace the wiring box cover and screws. Refer to Figure
18.
3. The furnace's control system requires correct polarity of the power
supply and a proper ground connection. Refer to Figure 19.
IMPORTANT: The power connection leads and wiring box may be relo-
cated to the left side of the furnace. Remove the screws and cut wire tie
holding excess wiring. Reposition on the left side of the furnace and fas-
ten using holes provided.
LOW VOLTAGE CONTROL WIRING CONNECTIONS
Install the field-supplied thermostat by following the instructions that
come with the thermostat. With the thermostat set in the OFF position
and the main electrical source disconnected, connect the thermostat
wiring from the wiring connections on the thermostat to the terminal
board on the ignition module, as shown in Figure 20. Electronic thermo-
stats may require the common wire to be connected as shown with the
dashed line in Figure 20. Apply strain relief to thermostat wires passing
through cabinet. If air conditioning equipment is installed, use thermo-
stat wiring to connect the Y and C terminals on the furnace control
board to the yellow and brown wires on the condensing unit (unit out-
side). Refer to Figure 20.
IMPORTANT: Some electronic thermostats do not have adjustable heat
anticipators. They may have other type cycle rate adjustments. Follow
the thermostat manufacturer's instructions.
IMPORTANT: Set the heat anticipator in the room thermostat to 0.40
amps. Setting it lower will cause short cycles. Setting it higher will cause
the room temperature to exceed the set points.
The 24-volt, 40 VA transformer is sized for the furnace components
only, and should not be connected to power auxiliary devices such as
humidifiers, air cleaners, etc. The transformer may provide power for an
air conditioning unit contactor.
SECTION VI: ACCESSORY CONNECTIONS
The furnace control will allow power-switching control of various acces-
sories. Refer to Figure 21 for connection details.
ELECTRONIC AIR CLEANER CONNECTION
Two 1/4” (0.6 cm) spade terminals (EAC and EAC N) for electronic air
cleaner connections are located on the control board. The terminals
provide 115 VAC (1.0 amp maximum) during circulating blower opera-
tion.
HUMIDIFIER CONNECTION
Two 1/4” (0.6 cm) spade terminals (HUM and HUM N) for humidifier
connections are located on the control board. The terminals provide 115
VAC (1.0 amp maximum) during heating system operation.
SECTION VII: TWINNING AND STAGING
NOTE: You can twin two furnaces that have the same integrated control
module. Check the part number on the integrated control mod-
ule. You cannot twin
two furnaces that have different integrated
control module part numbers. If the part numbers of the two inte-
grated control modules are different they may not communicate
with each other so they will not work in a twinning application.
In applications where more heating capacity or more airflow capacity is
needed than what one furnace can deliver, twinning can be used to
make two furnaces operate in tandem. When two furnaces are installed
using the same duct system, it is very important that the two furnace cir-
culating air blowers operate in unison. If one blower starts before the
second blower, the duct system will become pressurized and the blower
on the second furnace will turn backwards causing the second furnace
to overheat, resulting in damage to the furnace. Twinning is used to
make two furnaces operate in tandem, using one duct system, one
room thermostat and causing both furnaces to turn on and off simulta-
neously.
FIGURE 18: Electrical Wiring - Upflow Position
FIGURE 19: Line Wiring Connections
BLK
WHT
GRN
BLK (HOT)
WHT (NEUTRAL)
GRN
NOMINAL
120 VOLT
ROOM
THERMOSTAT
FURNACE
CONTROL
CONDENSING
UNIT
TO AIR CONDITIONER
CONTROLS
R
W
G
Y
C
R
W
G
Y
C
COMMON T’STAT CONNECTION
FIGURE 20: Two-Stage Heating and Cooling Thermostat Connections
FIGURE 21: Accessory Connections
Room
Thermostat
Furnace
Control
Condensing
Unit
To Air Conditioner
Controls
R
W
G
Y1
C
R
G
C
Common T’stat Connection
W
Y2
Y1
Y2
115 VOLT
HUMIDIFIER
115 VOLT
ELECTRONIC
AIR CLEANER
BLK
WHT
EAC HOT
HUM. HOT
BLK
WHT
EAC
HUM
EAC
HUM
NEUTRALS
SWITCHED
CIRCUITS