Installation manual
166753-UIM-C-0706
Unitary Products Group 9
SECTION V: ELECTRICAL POWER
SECTION V: ELECTRICAL POWERSECTION V: ELECTRICAL POWER
SECTION V: ELECTRICAL POWER
Electrical Power Connections
Field wiring to the unit must be grounded. Electric wires that are field
installed shall conform to the temperature limitation for 63°F (35°C) rise
wire when installed in accordance with instructions. Refer to Table 7 in
these instructions for specific furnace electrical data.
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.
TABLE 6:
Nominal Manifold Pressure - High Fire
Single/Second Stage Manifold Pressures (in wc) Single/Second Stage Manifold Pressures (kpa)
Altitude (feet) Altitude (m)
0-7999 8000-8999 9000-9999 0-2437 2438-2742 2743-3048
Gas Heating Value
(BTU/cu ft.)
800 3.5 3.5 3.5
Gas Heating Value
(MJ/cu m)
29.8 0.87 0.87 0.87
850 3.5 3.5 3.5 31.7 0.87 0.87 0.87
900 3.5 3.5 3.5 33.5 0.87 0.87 0.87
950 3.5 3.5 3.3 35.4 0.87 0.87 0.81
1000 3.5 3.2 2.9 37.3 0.87 0.80 0.73
1050 3.5 2.9 2.7 39.1 0.87 0.73 0.67
1100 3.2 2.7 2.4 41.0 0.80 0.66 0.61
2500 (LP) 9.8 8.2 7.5 93.2 (LP) 2.44 2.03 1.86
PROPANE AND HIGH ALTITUDE CONVERSION KITS
It is very important to choose the correct kit and/or gas orifices for the altitude and the type of gas for which the furnace is being installed.
Only use natural gas in furnaces designed for natural gas. Only use propane (LP) gas for furnaces that have been properly converted to use pro-
pane (LP) gas. Do not use this furnace with butane gas.
Incorrect gas orifices or a furnace that has been improperly converted will create an extremely dangerous condition resulting in premature heat
exchanger failure, excessive sooting, high levels of carbon monoxide, personal injury, property damage, a fire hazard and/or death.
High altitude and propane (LP) conversions are required in order for the appliance to satisfactory meet the application.
An authorized distributor or dealer must make all gas conversions.
In Canada, a certified conversion station or other qualified agency, using factory specified and/or approved parts, must perform the conversion.
The installer must take every precaution to insure that the furnace has been converted to the proper gas orifice size when the furnace is installed.
Do not attempt to drill out any orifices to obtain the proper orifice size. Drilling out a gas orifice will cause misalignment of the burner flames,
causing premature heat exchanger burnout, high levels of carbon monoxide, excessive sooting, a fire hazard, personal injury, property damage
and/or death.
Use copper conductors only.
TABLE 7:
Ratings & Physical / Electrical Data - Upflow Models
Input Output
Nominal
Airflow
Cabinet Width
Total Unit
Amps
AFUE
Air Temp. Rise
MBH kW MBH kW CFM cmm In. cm °F °C
40 11.7 32 9.4 1200 34.0 14-1/2 36.8 9.0 80.0 25-55 13-31
60 17.6 48 14.1 1200 34.0 14-1/2 36.8 9.0 80.0 25-55 13-31
80 23.5 64 18.8 1200 34.0 14-1/2 36.8 9.0 80.0 35-65 19-36
80 23.5 64 18.8 1600 45.3 17 1/2 44.5 12.0 80.0 25-55 13-31
80 23.5 64 18.8 1600 45.3 21 53.3 12.0 80.0 25-55 13-31
80 23.5 64 18.8
2000
2200
56.6
62.3
21 53.3 14.0 80.0 25-55 13-31
100 29.3 80 23.4 1200 34.0 17 1/2 44.5 12.0 80.0 40-70 22-39
100 29.3 80 23.4 1600 45.3 17 1/2 44.5 12.0 80.0 35-65 19-36
100 29.3 80 23.4 1600 45.3 21 53.3 12.0 80.0 35-65 19-36
100 29.3 80 23.4 2000 56.6 21 53.3 14.0 80.0 25-55 13-31
115 33.7 92 26.9 1600 45.3 21 53.3 12.0 80.0 35-65 19-36
115 33.7 92 26.9 2000 56.6 21 53.3 14.0 80.0 30-60 17-33
130 38.1 104 30.5 2000 56.6 24-1/2 62.2 14.0 80.0 35-65 19-36
Input
Max. Outlet
Air Temp
Blower
Blower
Size
Max
Over-Current
Protect
Min. wire Size
(awg) @ 75 ft
one way
Operation
WGT.
Operation
WGT.
MBH kW °F °C Hp Amps In. cm LBS Kg
40 11.7 155 68.3 1/2 7.1 10 x 8 25.4 x 17.7 20 14 105 47.6
60 17.6 155 68.3 1/2 7.1 10 x 8 25.4 x 17.7 20 14 110 49.9
80 23.5 170 76.7 1/2 7.1 10 x 8 25.4 x 17.7 20 14 117 53.1
80 23.5 155 68.3 3/4 11.5 11 x 8 27.9 x 20.3 20 14 126 57.2
80 23.5 155 68.3 3/4 11.5 10 x 10 25.4 x 25.4 20 14 130 59.0
80 23.5 165 73.9 1.0 14.0 11 x 11 27.9 x 25.4 20 12 140 63.5
100 29.3 170 76.7 1/2 7.1 10 x 8 25.4 x 20.3 20 14 128 58.1
100 29.3 165 73.9 3/4 11.5 11 x 8 25.4 x 25.4 20 14 134 60.8
100 29.3 165 73.9 3/4 11.5 10 x 10 25.4 x 25.4 20 14 140 63.5
100 29.3 155 68.3 1.0 14.0 11 x 11 27.9 x 25.4 20 12 145 65.8
115 33.7 170 76.7 3/4 11.5 10 x 10 25.4 x 25.4 20 14 145 65.8
115 33.7 170 76.7 1.0 14.0 11 x 11 27.9 x 25.4 20 12 147 66.7
130 38.1 165 73.9 1.0 14.0 11 x 11 27.9 x 25.4 20 12 158 71.7