Specifications

Chalet 1800 20
RESIDENTIAL INSTALLATION (cont’d)
11) In seismically active areas, Archgard recommends that your unit be secured to the floor by using
¼” lag bolts in the bolt down holes on the pedestal or legs (the same ones used for Mobile Home
installations).
12) For residential installations using 6" "C" Vent (single wall), the chimney connector must be at least
24 gauge steel. Do not use galvanized pipe. For Mobile Home installation, use only listed air
insulated double wall connector.
13) Do not connect this unit to a chimney serving another
appliance.
14) A chimney connector cannot pass through an attic or roof
space, closet or similar concealed space, or a floor, ceiling,
wall or partition of combustible construction. In Canada, if
passage through a wall, or partition of combustible
construction is desired, the installation shall conform to CAN/
CSA-B365, Installation Code for Solid-Fuel-Burning
Appliances and Equipment. In the U.S.A. install according to
NFPA 211.
Do not connect your Archgard Woodstove to an air distribution
duct.
Check with chimney manufacturer’s installation instructions for
more thorough / detailed instructions for installing their chimney
Horizontal Installation Vertical Installation