6.3.8.1. Disable Zoning
This option allows the installer to enable or disable zoning. After the selection is
made, touch SAVE.
S Disable Zoning: Yes or No
d Default = No
6.3.8.2. Zone Offsets
This option allows actual temperature offset for each zone, allowing calibration (or
deliberate miscalibration) of each sensor. Use the Left (<) or Right (>) buttons to
change the zone. After the selection is made, touch SAVE.
S Temperature Offset: Adjustable between --5 to 5_F(--3to3_C)
d Default = 0_F
6.3.8.3. Airflow Lim its
Since a bypass damper is prohibited in this system, this setting is used to select the
maximum allowable noise/airflow relationship into each zone based on air noise
and comfort requ irements. LOW means 100% of maximum assessed airflow;
MED--LOW means 138% of maximum assessed airflow; MEDIUM means 176%
of max imum assesse d airflow; MED--HIGH means 214% of maximum assessed