Installation Manual

60
S Heat Pump: Disabled, Low Stage or Turn off
d Default = Disabled
6.3.11. Hydronic Airflow
NOTE: The daily duct assessment will occur even if Hydronic Airflow is set to
Off. This is done to ensure that the system will continue to provide proper airflow
for all installed equipment, since duct system changes may occur at any time, such
as opened or closed registers.
This option allows the installer to select the airflow for the fan coil when paired
with a hydronic coil. After the selections are made, touch SAVE.
A12194
S Airflow: Selectable between Off to Max in 50 CFM increments
d Default = Off, 500 CFM, Max = (odu_size in KBTU * 400/12)
NOTE: Selected airflow used during hydronic heating is a fixed value, it does not
vary.
S Blower On Delay: Selectable from 0 to 240 seconds
d Default = 30 seconds
S Blower Off Delay: Selectable from 0 to 240 seconds
d Default = 0 seconds