Fig. 17 -- Remote Room Sensor -- Parallel Wiring
This selection determines which sensor the Thermostat will use for measuring room air
temperature. Room air temperature can be sensed in one of three ways; the local sensor (L)
located on the Display Module, the remote room air sensor (r), or the average of local and remote
sensors (Lr). Settings are L, r, Lr.
Default is L.
SW06 Cooling Lockout Below 55F /13C
This selection disables cooling when outdoor temperature is below 55F /13C. It requires an
outdoor temperature sensor or Wi-Fi connection with internet weather (internet through Wi-Fi is
required and the unit must be registered with location information entered to obtain internet
weather). Setting is not available if valid outdoor sensor is not connected or the thermostat not
receiving internet weather information. Set to OFF to allow cooling below 55F /13C. Set to On
to prevent cooling below 55F /13C.
Factory default is OFF
SW07 Zoning
This selection should be set to On when the Thermostat is to be used as part of a zoning system.
It is assumed that the zoning equipment will take care of time guard and cycle timers. The
minimum On time is still controlled by the Thermostat.
Default is OFF
SW08 Auxiliary Heat Lockout Temperature
This selection is available on heat pump systems with a valid outdoor temperature sensor
connected or Wi-Fi connection with internet weather setup. Available settings are: Off, 5, 10, 15,
20, 25, 30, 35, 40, 45, 50, 55.