User's Manual

27
be performed. When the value reaches zero, the room air temperature shall display Fd and
“RESETTING..” in the text box. When the factory defaults have been restored, the Thermostat
will act as if power was cycled and return to normal operation. If the DOWN key is released
early, the number will return to 10 and the reset will not occur.
Note: if you reset to factory defaults you will need to reconfigure the thermostat for the
connected equipment. To reset homeowner preferences exit the dealer setup menu and select
menu from the home screen then select settings and go to item 14 “RST DEFAULT” to reset
user preferences.
SYSTEM START-UP AND CHECKOUT
The Thermostat is designed with a built-in installer test capability. It allows easy operation of
equipment without delays or setpoint adjustments to force heating or cooling. To enable installer
test capability called Output Test mode, press and hold the fan button for 10 seconds. Pressing
the Heat/Cool button will change the system operating mode to test the heating and cooling
equipment based on the equipment setup. Auto Mode is not available during Installer Test Mode.
If no buttons are pressed for 15 minutes, the installer test mode will be terminated. Pressing
Heat/Cool mode button will stop the test but remain in Output Test model Pressing DONE or
START at any time will exit installer test mode.
Aux Heat The first stage of Aux Heat will be energize for three minutes, then the first and
second stages (if a second stage exists) will turn on for an additional three minutes. The Aux
Heat icon at the top of the screen will be displayed and a text message on the screen will display
STG 1 and count down from 180 seconds. After three minutes the thermostat will go back to
Heat/Cool mode to Off. If no buttons are pressed for 15 minutes, the installer test mode will be
terminated.
Heat The first stage of heating will be energized for three minutes, then the first and second
stages (if a second stage exists) will turn on for an additional three minutes. During the first stage
of heating, the HEAT icon will be displayed along with the text “STG 1”. During the second
stage of heating (if one exists), the “STG 2” text will be displayed if the system has a two-stage
compressor (A2, h2, or H2 unit types). The “auxiliary heat on” icon will be displayed if the
second stage is electric heat (HP unit type). While the heating test is active, the fan output
(accessory output on the Côr 7 series) can be toggled by pressing Menu then the up/dn arrows to
select.
Output Test for cooling is the same as described for heating above. The COOL icon and the
stage text will be displayed during cooling in Installer Test Mode. While the cooling test is
active, the fan output (and accessory output on the Côr 7 series) can be toggled by pressing Menu
then the up/dn arrows to select and toggle them on/off.
TO TEST FAN