Specifications
Electrical Commissioning
Cable Requirements
Compac Industries Ltd.
Page 9
www.compac.co.nz
Electrical Commissioning
Cable Requirements
Cable requirements are as follows:
Cable Type
Requirements
Power
3 Core Steel Wire Armour Cable 2.5mm
2
,
220 - 240 Volts. 50 Hz, +/-10%
Core 1: 230 Volt Supply (Active).
Core 2: Neutral.
Core 3: Earth.
Dispenser:
25w Idle, 200W with all solenoids active.
Pumps with one motor (40 and 80 lpm Single hose)
Motor start current = 30 amps, run current = 6 amps
Pumps with two motors -40 and 80 lpm Dual pumps and 160 lpm
Single hose pumps
Motor start current = 30 amps, run current = 6 amps
(software prevents both motors starting simultaneously)
Comms
2 Core Steel Wire Armour Cable 1.5 mm
2
. Maximum cable length 100 m.
12 V current loop.
Make sure that there is at least a two metre cable tail on
both the incoming underground 230 V and comms cables to reach the
C4000 flameproof box.