UPG Data Sheet
Absorbant Glass Mat (AGM) technology for superior performance. Valve regulated, spill proof construction allows safe
operation in any position. Approved for transport by air. D.O.T., I.A.T.A., F.A.A. and C.A.B. certied. U.L. recognized under le
number MH 20567.
Sealed Lead-Acid Battery
488 S. Royal Lane Coppell, Texas 75019 P 469.892.1122 T 866.892.1122 F 469.892.1123 sales@upgi.com
www.upgi.com
Nominal Voltage
Nominal Capacity
20-hr. (2.50A)
10-hr. (4.65A)
5-hr. (8.50A)
1-hr. (30.0A)
Approximate Weight
Internal Resistance (approx.)
Shelf Life (% of normal capacity at 68º F (20º C)
3 Months 6 Months 12 Months
12 volts
50.0 Ah
15 A or smaller
14.6 - 14.8 V
77º F (25º C)
46.5 Ah
42.5 Ah
30.0 Ah
30.2 lbs (13.7 kgs)
11 m1
91% 83% 64%
Charge Method (Constant Voltage)
Cycle Use
Float Use
Initial Current
Control Voltage
13.6 - 13.8 V
Control Voltage
(Repeating Use)
Specification
Physical Dimensions: in (mm)
F2007-1
UPG No. 45979
Maintenance-Free
UB12500
L: 7.76in (197.05mm)
W: 6.53in (165.81mm)
H: 6.84in (173.76mm)
TH: 6.9in (175.38mm)
Tolerances are +/- 0.04 in. (+/- 1mm)
and +/- 0.08 in. (+/- 2mm) for height
dimensions. All data subject to
change without notice.
7.76 (197.05)
6.53 (165.811)
6.841 (173.76)
6.9 (175.38)
Due to continuous improvements to our products, product may vary slightly from depiction.
Temperature Dependency of Capacity
104 F (40 C) 77 F (25 C)
(20 hour rate)
102% 100% 85%
32 F (0 C) 5 F (-15 C)
65%
AGM Operational Temperature
AGM Storage Temperature
(0 C to 40 C)32 F to 104 F
5 F to 113 F
5 F to 104 F
(-15 C to 45 C)
Charge
Discharge
(-15 C to 40 C)
All specifications are subject to change without notice.
1.60V 210.0 91.0 55.1 30.8 17.9 12.68 8.80 5.63 4.72 2.59
1.67V 202.0 89.0 53.8 30.5 17.5 12.63 8.73 5.60 4.68 2.57
1.70V 195.0 88.4 53.3 30.0 17.3 12.54 8.67 5.58 4.65 2.50
1.75V 181.0 85.8 51.7 29.3 16.8 12.49 8.50 5.55 4.57 2.45
1.80V 163.0 82.8 49.7 28.2 16.2 12.15 8.26 5.52 4.46 2.41
1.60V 2124.0 1022.0 613.0 360.0 215.0 154.0 107.0 78.24 58.60 32.00
1.67V 2060.0 997.0 597.0 353.0 212.0 150.0 106.0 77.65 58.10 31.50
1.70V 2031.0 981.0 590.0 350.0 207.0 148.0 105.0 76.47 57.70 31.20
1.75V 1895.0 940.0 571.0 342.0 200.0 143.0 104.0 75.88 56.30 31.00
1.80V 1693.0 882.4 528.0 332.0 192.0 136.0 103.0 74.71 54.60 30.30
Constant Current Discharge Characteristics Unit: A (25 C, 77 F)
Constant Power Discharge Characteristics Unit: W (25 C, 77 F)
F.V/Time 5MIN 15MIN 30MIN 60MIN 2HR 3HR 5HR 8HR 10HR 20HR
F.V/Time 5MIN 15MIN 30MIN 60MIN 2HR 3HR 5HR 8HR 10HR 20HR