As a refrigeration contractor or a planning engineer you often have the
problem to get the right cold storage controller that fits perfectly to your
application. By using the TKP3130 this problem is no longer the issue, since
this controller is designed to be universal. Its ‘free c o n f i g u r a b l e’ concept
enables you to use it for almost all refrigeration applications.
The ‘free configurable’ concept means that all controller inputs and outputs
(
6 relays, 6 sensors, 4 digital (OC)-inputs, 1 analog output
) can be configured
to work with any integrated control functions or control circuits.
Sensors
Each sensor can fulfill each function, even up to 3 functions at the same time
(function sensor X a, function sensor X b, function sensor X c, X = sensor no.).
e.g. cold store
: function sensor 1 is:
1a: control sensor and
1b: alarm sensor
or refrigerated shelf: function sensor 1 is:
1a: control sensor,
1b: defrost sensor and
1c: alarm sensor.
Digital Inputs (OptoCoupler Inputs)
Each digital input can be assigned to one of the possible functions.
Relay Outputs
Each relay can be used to control one of the possible functions. The same
function can even be allocated to multiple relays.
Parameters
Parameters of functions which are not assigned will not appear in the
parameter pages to improve survey.
Assignment
The function of each input and output can be preset on the 'assignment page'.
The assignment can be done by the keys or via interface.
Example of a configuration for a freezer with 3 evaporators:
Configuration Concept
Configuration of the controller
Hereby we use the example from above: freezer with 3 evaporators
action key display remarks
select assignment page "ñò"
enter assignment page "PROG"
select desired output "PROG" at the beginning of programming only, or after
no key is pressed for about 3 minutes
enter code depending on time "ñò"
confirm "PROG" flashing
select function for this output "ñò" flashing
confirm "PROG" flashing stops, relay already working
select new input/output "ò"
prepare for programming "PROG" flashing
select function for this output "ñò" flashing
confirm "PROG" flashing stops, relay already working
select new input/output "ò"
prepare for programming "PROG" flashing
select function for this output "ñò" flashing
confirm "PROG" flashing stops, relay already working
Repeat this steps until all inputs and outputs are assigned to the desired functions.
assignment page
05.06.01 14:10
function relay 1
---
identification
Enter :> 0 <
function relay 1
---
function relay 1
alarm
function relay 1
alarm
function relay 2
---
function relay 2
---
function relay 2
refrig. 1
function relay 2
refrig. 1
function relay 3
---
function relay 3
---
function relay 3
fan 1
function relay 3
fan 1
TKP/TKC
allocation of
inputs-/outputs
1: alarm sensor 1........
2: .................................
3................................
manual defrost
Regler AUS
Sollwertebene 2
night settings
1: defrost sensor 13...
2: ................................
3...............................
OC 1
OC 3
OC 4
OC 2
sensor 6
sensor 5
1: defrost sensor 11
2: .............................
3.............................
1: alarm sensor 1......
2: ...............................
3................................
1: defrost sensor 12
2: ...............................
3...............................
1: control sensor 1....
2: alarm sensor 1.....
3..............................
sensor 4
sensor 3
sensor 2
sensor 1
relay 6
defrost 1/1
actual value image
analog
fan
relay 5
relay 4
defrost 1/2
defrost 1/3
relay 3
relay 2
relay 1
refrig. 1
alarm