Submittal Sheet

Engineered Plastic (EP) Heating Manifold Assemblies
Submittal Information
Revision A: Dec. 1, 2008
Project Information
Job Name:
Location: Part No. Ordered:
Engineer: Date Submitted:
Contractor: Submitted By:
Manufacturer’s Representative: Approved By:
Technical Data
Manifold, Connecting
Piece, Elbow, End Part:
PA66-GF30
Max. Test Pressure
(24 h, 86°F) tested
with water:
145 psi
(10 ba
r
)
Bracket, Locking
Screw:
PA66-GF15 Max. Test Pressure
(24 h, 70°F) tested
with air:
100 psi (7 bar)
Valve Insert (all plastic
parts), Handwheels:
POM
Max. Water Flow per
Manifold:
0.97 l/s 15.4 gpm
Adjusting Screen:
ABS Cv Value Inlet/Outlet
Valves:
1.35
Glass Flow Meter PA12 Spring:
Stainless Steel
Metal Inserts:
Brass C38500
O-ring: EPDM
Axel:
Stainless Steel Flat Gasket: I
T
-C
Adaptable Actuators: EP Heating Manifold, two-wire Actuator (A3030522);
Thermal Actuator, four-wire (A3010522) with EP Heating
Manifold Actuator Adaptor (A2671300)
Max. Operating Temperature
and Pressure:
6 bar at 60°C
87 psi at 140°F
5 bar at 70°C
72 psi at 158°F
4 bar at 80°C
58 psi at 176°F
3 bar at 90°C
44 psi at 194°F
Product Information and Application Use
The Engineered Plastic (EP) Heating Manifold Assemblies feature isolation valves and
balancing valves with flow meters, and come fully assembled, ready for installation in
hydronic radiant heating and cooling systems. The manifolds are available in 2 through 8
loops, the body ends feature R32 unions and the loop outlets have R20 male threads. The
manifold mounts on a bracket (A2670006) that comes with the assembly. Use only propylene
glycol in radiant systems with EP Heating Manifolds; never use ethylene glycol.
9
Description
Part
Number
Height Width Depth Weight
EP Heating Manifold Assembly with Flow Meter, 2-loop
EP Heating Manifold Assembly with Flow Meter, 3-loop
EP Heating Manifold Assembly with Flow Meter, 4-loop
EP Heating Manifold Assembly with Flow Meter, 5-loop
EP Heating Manifold Assembly with Flow Meter, 6-loop
EP Heating Manifold Assembly with Flow Meter, 7-loop
EP Heating Manifold Assembly with Flow Meter, 8-loop
A2670201
A2670301
A2670401
A2670501
A2670601
A2670701
A2670801
14.0"
14.0"
14.0"
14.0"
14.0"
14.0"
14.0"
9.6"
11.6"
13.6"
15.6"
17.6"
19.5"
21.5"
2.7"
2.7"
2.7"
2.7"
2.7"
2.7"
2.7"
3.50 lbs.
4.16 lbs.
4.82 lbs.
5.48 lbs.
6.14 lbs.
6.80 lbs.
7.46 lbs.
Installation
Do not use thread sealant on connections. Carriers present in these compounds can crack the plastic port connections, resulting in leaks and water
damage. For additional information, refer to the EP Heating Manifold Instruction Sheet
. Note: Use only propylene glycol in radiant heating and cooling
systems with EP Heating Manifolds; never use ethylene glycol. Refer to the EP Heating Manifold Installation Guide for a complete chemicals list.
Standards/Codes/Listings
N/A
Related Applications Contact Information
Radiant Heating and Cooling Systems
Snow and Ice Melting Systems
Permafrost Protection Systems
Turf Conditioning Systems
Uponor, Inc.
5925 148
th
Street West
Apple Valley, MN 55124 USA
Phone: (800) 321-4739
Fax: (952) 891-2008
www.uponor-usa.com
Uponor Ltd.
2000 Argentia Road, Plaza 1, Suite 200
Mississauga, ON L5N 1W1 CANADA
Phone: (888) 994-7726
Fax: (800) 638-9517
www.uponor.ca

Summary of content (1 pages)