INDOOR CLIMATE CLIMATE CONTROLLER C- 46 Installation and operation manual 11 | 2010
Contents 1 6.2.8 Switch mode .................................................... 18 Copyright and Disclaimer ............................ 4 6.2.9 Mixing valve mode ........................................... 18 Restarting the installation wizard ..................... 18 2 Preface ........................................................... 5 6.3 2.1 Safety instructions ........................................... 5 6.4 Operation .........................................................
8.5.1 Supply setpoint ................................................ 24 8.12.7 General purpose output................................... 39 8.5.2 Indoor setpoint ................................................ 24 8.12.8 GPO status ...................................................... 40 8.5.3 Average setpoint .............................................. 25 8.12.9 Controller ID .................................................... 40 40 8.5.4 Min./Max. supply..........................
1 Copyright and Disclaimer Uponor has prepared this Uponor Control System Installation and Operation Manual and all the content included solely for information purposes. The contents of the Manual (including graphics, logos, icons, text, and images) are copyrighted and protected by worldwide copyright laws and treaty provisions. You agree to comply with all copyright laws worldwide in your use of the Manual.
2 Preface The Uponor Climate Controller installation manual describes how to install and operate the components of the system. Example applications and possible configurations of the system are also included. affecting radio communication and maximum transmission distance. If communication difficulties exist, Uponor can support the system with accessories, such as repeaters, for solving exceptional problems. 2.1 2.
3 Climate Controller C-46 overview This section is a brief description of the Climate Controller C-46 as a system component and its operating modes. 3.1 Description The Climate Controller C-46 is a primary controller for heating, cooling and meltaway systems.
3.1.2 Meltaway example The figure below shows how the Climate Controller C-46 can be set up in a meltaway system. The figure also shows several system components that can be connected to the Climate Controller C-46. NOTE! Only Uponor sensors and should be used in combination with the Climate Controller C-46. 3.2.
Setpoint adjustment and definitions are the same as for the case with radio thermostats connected to the Climate Controller C-46, see above. 3.2.5 Sensor priorities When sensors and thermostats are connected to the Climate Controller C-46 in different ways, the following priorities apply: 1. Thermostats linked to the Climate Controller C-46 through an antenna have the first priority. Heating – fixed supply In this operating mode, the Climate Controller C-46 maintains a constant supply temperature.
• Setting of Min./Max. supply parameter, see section 6.2.4 Heating, page 16 • Setting of Indoor sensor influence parameter, see section 8.5.8 Indoor sensor influence, page 26 Heating – outdoor controlled average In this operating mode, the Climate Controller C-46 adjusts the supply temperature depending on the average supply–return temperature. When the parameters are set, the indoor temperature will be kept at a constant level. See also section 10.2 Adjusting the heat curve, page 46.
3.3.4 Operating modes and sensor use The table below shows which sensors are used in which operating mode.
It is possible to select any of the available heating modes for the heating function and any of the available cooling modes for the cooling function. See sections above. H/C switchover in slave mode In this switchover mode, the Climate Controller C-46 switches between heating and cooling mode controlled from an external source.
4 System integration of Climate Controller C-46 and Controller C-56 Radio The Climate Controller C-46 can be integrated with the Controller C-56 Radio to enhance the capabilities of the climate system. The illustration below shows an example configuration. NOTE! The Controller C-56 Radio must be equipped with software version 5.0.3 or later to work correctly in connection with Climate Controller C-46. Controllers C-56 Radio with assembly date 4010 or later have the correct software version.
5 5.1 Installing Climate Controller C-46 Preparing the installation Follow the guidelines below to determine the best installation position: 1. Study the connection diagrams of the Climate Controller C-46, see section 5.4 Connecting the Climate Controller C46, page 14. 5.3 Wall-mounting the Climate Controller C-46 The Climate Controller C-46 is delivered in a kit including screws and wall plugs. The figure below shows the Climate Controller C-46 dimensions and the mounting hole positions. 2.
5.4 Connecting the Climate Controller C-46 Connections of sensors and other equipment is made in both the lower and upper compartments. Upper compartment The figure below shows an example of cable connection in the upper compartment. On top of the illustration is the cover inside with label. Lower compartment The figure below shows an example of cable connection in the lower compartment.
6 Setting Up the Climate Controller C-46 The Climate Controller C-46 features a four row display and a set of navigation keys for the operation. 6.1 Key Functions OK Displays next screen Operation interface The Climate Controller C-46 operating interface is shown in the figure below. 6.1.2 or Confirms selections; displays current menu Alarm indicator The alarm indicator flashes in case there is any alarm detected in the Climate Controller C-46. See section 8.11.1 All alarms, page 37. 6.1.
The following screen is displayed as default in basic access level: Pos. Icon Description 7 Comfort mode Economy mode 6.2 Installation wizard When the Climate Controller C-46 is started the very first time, it will guide the operator to make the necessary primary settings of the system. The installation wizard is also started after changing or resetting the operating mode. Pos. Icon Description 1 Basic access level 6.2.1 Installer access level 1.
1. Use the navigation keys to highlight a sensor to be used. 2. Press OK to select the sensor. 3. Press OK again to clear a selection if necessary. 4. Navigate to the OK field and press OK to display the next screen. 5. In the screen Min./max. supply, set the required minimum and maximum temperatures in the supply circuit. 5. In the screen Min./max. supply, set the required minimum and maximum temperatures in the supply circuit.
The next screen is displayed, see section 6.2.9 Mixing valve mode, page 18. 6.2.7 H/C switchover The internal system bus is used to control the heating/cooling swithover function when a Controller C-56 Radio is connected to the Climate Controller C-46.
7 Quick menu The Quick menu consists of a series of screens easily accessible from the Uponor screen. These screens displays readings for daily use. If the Climate Controller C-46 is set to Installer access level, it is also possible to modify some parameters. For a full access to all screens in the Climate Controller C-46, see section 8 Operating the Climate Controller C-46, page 22.
7.3 Parameter screens The parameter setting screens can only be accessed when the Climate Controller C-46 is set up in Installer access level. 7.3.1 Parameter values: • • Default setting: 0.2 Parameter range: 0.1–1.6 Navigating parameter screens To navigate through the parameter setting screens: 7.3.6 1. Press OK for two seconds to highlight the parameter. The T-adjustment parameter can be set if the Climate Controller C-46 is set up in any Heating – outdoor controlled mode. 2.
7.3.10 Dew point margin The Dew point margin can be set if the Climate Controller C-46 is set up in any Cooling mode. Parameter values: • • Default setting: 4 Parameter range: 1–10 7.3.11 Dew point offset The Dew point offset can be set if the Climate Controller C-46 is set up in any Cooling mode. Parameter values: • • Default setting: 0 Parameter range: -5 to +5 7.3.12 Calculated dew point The dew point is the temperature when water vapour in the air condenses into water.
8 Operating the Climate Controller C-46 This section describes the screens that are used for The Climate controller menu contains the following items: • • • • • • • • • • • • setting parameters to operate the system selecting operating modes and sub-modes displaying parameter settings displaying selected operating modes displaying sensor readings NOTE! All sequences described below start from the Uponor screen. 8.2.1 Operating mode, section 8.2.1, page 22 Supply temperature, section 8.2.
8.2.4 Average temperature Example screen: The average temperature is the mean value of supply temperature and return temperature. It can be displayed if both a supply sensor and a return sensor are used. To display the average temperature: 1. Navigate through the screens using the navigation keys: Uponor > Main menu > Climate controller > Average temperature Example screen. 8.
8.4.1 Standby mode The Climate Controller C-46 can be set in standby mode to temporarily disable all controlling functions. However, it will still be possible to read measurements from the connected thermostats and sensors. In standby mode it is possible to manually exercise the mixing valve mixing valve and pump, see section 8.9.8 Valve and pump exercise, page 33. To set the Climate Controller C-46 in standby mode: • • • • • • T-adjustment, section 8.5.6, page 25 Supply information, section 8.5.
8.5.3 Average setpoint The average setpoint is the mean value of supply and return temperatures that the system regulates to reach. To set the average setpoint: 1. Navigate through the screens using the navigation keys: Uponor > Main menu > Control settings > Heating > Average setpoint For more information, see section 10.2 Adjusting the heat curve, page 46. To set the T-slope parameter: 1.
8.5.7 Supply information The Supply information can be displayed if the Climate Controller C-46 is set up in any Heating – outdoor controlled mode. 1. Navigate through the screens using the navigation keys: Uponor > Main menu > Control settings > Heating > Indoor sensor mode Example screen: The supply information is used as a tool when adjusting the heat curve with the T-slope and T-adjustment parameters. The screen displays the supply temperature for four different outdoor temperatures.
2. Select Act./deact. temp. 3. Set the parameter to the required value and press OK. To set the supply setpoint: 1. Navigate through the screens using the navigation keys: Uponor > Main menu > Control settings > Cooling > Supply setpoint Example screen: 4. Select Delay. 5. Set the parameter to the required value and press OK. 2. Select the desired set-point. 6. Select Shut-off enable period. 7. Set the parameter to the required value and press OK.
8.6.3 Min./Max. supply 1. Navigate through the screens using the navigation keys: The parameters Min./Max. supply are used for setting the minimum and maximum temperatures in the supply circuit. Uponor > Main menu > Control settings > Cooling > Dew point To set the minimum and maximum supply temperatures: Example screen: 1. Navigate through the screens using the navigation keys: Uponor > Main menu > Control settings > Cooling > Min./max. supply Example screen: 2. Select Dew point margin 3.
8.6.6 Cooling activation When the Climate Controller C-46 is working in Cooling or Heating and cooling mode it is possible to set the Climate Controller C-46 to be either always active or to utilize a winter shut-off mode. To set the cooling activation mode: 1. Navigate through the screens using the navigation keys: Uponor > Main menu > Control settings > Cooling > Cooling activation 2. Select Winter shut-off or Always active and press OK to confirm the selection.
8.7 H/C switchover • When the Outdoor-indoor/supply temp. mode is selected, then continue with section 8.7.2 Outdoorindoor/supply temp. to set the required parameters. The H/C switchover menu is accessible when the Climate Controller C-46 is set to Heating + cooling operating mode. To set the H/C switchover parameters, do this: • 1. Navigate through the screens using the navigation keys: Supply temp. active When the Supply temp. active mode is selected, then continue with section 8.7.
8.7.3 Supply water temp. When the Supply temp. active mode is selected, then the following parameters must be set: 1. Select Supply temperature and press OK. Set the parameter to the required value and press OK. • • • Default setting: 18 °C Setting range: 5–30 °C Setting accuracy: 1 °C 2. Select Hysteresis and press OK. Set the parameter to the required value and press OK. • • • 8.
8.9.2 Control response The Control response parameters are used to adjust the control loop in the system. NOTE! It is recommended that at least one of the parameters is set above zero. To set the Control response parameters: 1. Navigate through the screens using the navigation keys: Uponor > Main menu > Control settings > Advanced control > Control response Example screen: • • Setting range: 1–100 min Setting accuracy: 1 min 3. Confirm the setting by pressing OK. 8.9.
8.9.5 Mixing valve Example screen: The Mixing valve menu is used to select between thermal and motorized actuator to control the mixing valve. To set the Mixing valve parameters: 1. Navigate through the screens using the navigation keys: Uponor > Main menu > Control settings > Advanced control > Mixing valve Example screen: 2. Select the required operation and press OK. Operation alternatives: • • 8.9.8 2. Select Mixing valve mode. 3. Select as required and press OK.
8.9.9 Pump management The Pump management menu is used to set how the circulation pump will be controlled. To select the Pump management control function, do this: 1. Navigate through the screens using the navigation keys: Uponor > Main menu > Control settings > Advanced control > Pump management Example screen: 2. In the ECO mode menu, select the required item and press OK. • • 8.10.1 Heating, proceed with section 8.10.1, page 34. Cooling, proceed with section 8.10.2, page 36.
• • • Apply ECO profiles This function is used to set which ECO profile to apply for each day of the week. ECO night and day ECO night ECO Custom To set the ECO profiles: 1. Navigate through the screens using the navigation keys: Uponor > Main menu > ECO mode > Heating > Apply ECO profiles The next screen displays graphically the time scheme for switching between comfort and economy modes: Example screen: 2. Use the and keys to select which day of the week the new ECO profile shall be applied to. 3.
8.10.2 Cooling To display the Cooling menu under ECO mode: 1. Navigate through the screens using the navigation keys: Uponor > Main menu > ECO mode > Cooling Example screen: 4. If more than one day shall be applied with the same ECO profile, then select the next day for the same ECO profile and make a short click with the key. Proceed in the same manner until all required days have been marked. 5. Press the key for several seconds until the screen ECO profiles list is displayed. 6.
Pos. Description 1 Time setting at the time cursor position, HH:mm 2 ECO or COMF indicator at the time cursor position 3 Time cursor, 30 minute step 4 High columns indicating comfort mode (COMF) 5 Short columns indicating economy mode (ECO) 6 Time scale, every 6 hours indicated with digits, high or short columns for every 30 minutes 3. Move the time cursor along the time scale with the and keys until the required 30-minutes time interval is reached. 4.
8.12.1 Example screen: Access level The Basic access level includes all functions necessary for daily use. To reach functions to change or adjust the set-up of the system, the Installer access level is used. 2. Select the desired time format and press OK. To change the access level, do this: 1. Navigate through the screens using the navigation keys: Uponor > Main menu > General settings > Access level Example screen: 2. Select the required access level and press OK. 8.12.
Setting fixed dates for daylight saving time To change the backlight mode, do this: To set fixed dates for daylight saving time, do this: 1. Navigate through the screens using the navigation keys 1. Set the required start and end dates and press OK. Uponor > Main menu > General settings > Backlight Example screen: 2. Select the required backlight mode and press OK. 8.12.3 Language The Language menu can be used to change the language used on the display of the Climate Controller C-46: 1.
8.12.8 GPO status Example screen: To display the General purpose output status: 1. Navigate through the screens using the navigation keys: Uponor > Main menu > General settings > General purpose output Example screen: 2. Select Yes or No and press OK to confirm. The General purpose output is set to off. 8.12.10 Software version To display the software version of Climate Controller C-46, do this: 1. Navigate through the screens using the navigation keys: 8.12.
8.13.1 View links The View links menu is used to display which sensors that are linked by radio to the Climate Controller C-46. It is also possible to display the working conditions for the radio linked sensors. 8.13.3 Reset all links To reset all established links: 1. Navigate through the screens using the navigation keys: To display the View links menu: Uponor > Main menu > General settings > Radio links > Reset all links 1.
9 Menu structure The tables below shows how to reach all menus in the Climate Controller C-46. Climate Controller C-46 screen Referenced section Uponor section 6.1.5 Display, page 15 Main menu section 8.1 Main menu, page 22 Climate controller Operating mode section 8.2.1 Operating mode, page 22 Supply temperature section 8.2.2 Supply temperature, page 22 Return temperature section 8.2.3 Return temperature, page 22 Average temperature section 8.2.
A = Main menu B = Main menu > Control settings H/C switchover section 8.7 H/C switchover, page 30 Bus master section 8.7 H/C switchover, page 30 Bus slave section 8.7 H/C switchover, page 30 No bus section 8.7 H/C switchover, page 30 Meltaway section 8.8 Meltaway, page 31 Advanced control section 8.9 Advanced control, page 31 Operating mode section 8.9.1 Operating mode (select), page 31 Control response section 8.9.2 Control response, page 32 Filtering temp. constant section 8.9.
10 Hints and examples This section describes a number of hints and examples to help the user to set up the heating and/or cooling system. 10.1 Economy and comfort modes The economy mode (ECO) is used to save energy. In heating mode, the economy mode reduces room temperatures with a given setback temperature. In cooling mode, the temperature is increased. Different economy profiles may be applied for the days of the week.
10.1.3 Eco night mode profile. When the Climate Controller C-46 is set to Eco night mode, this means that the temperature is temporarily lowered with the temperature setback value during night. The diagram below illustrates this by indicating that the temperature is lowered to economy level between 22.30 hours and 06.30 hours. Thursday Friday Profile: Eco custom 00:00 – 08:00 Economy mode 08:00 – 10:00 Comfort mode The figure to the right shows the ECO night screen for this case.
10.2 Adjusting the heat curve Default settings When the Climate Controller C-46 is set in Heating mode and an outdoor sensor is connected, the heat curve is adjusted to achieve an even zone temperature. When the Heating – outdoor controlled supply mode has been selected, the Climate Controller C-46 is set up with the following default values: 10.2.1 • • Description The two parameters T-slope and T-adjustment are used to adjust the heat curve: • T-slope = 0.
10.3 Heating summer shut-off and cooling winter shut-off The use of the heating summer shut-off and cooling winter shutoff features is described by a number of operation examples with instructions how to set up the system. The operation examples below require that the following prerequisites are met: • • The Climate Controller C-46 is installed as a stand-alone unit The Pump management function is set to Internal control mode, see section 8.9.
10.3.3 Cooling mode without winter-shut-off The diagram in the figure below, labelled Cooling mode without winter shut-off, illustrates an operation example with the following setup: • Operating mode is set to cooling, see section 8.9.1 Operating mode (select), page 31 • Winter shut-off is not defined Period P1: During this period, which covers the full year, the circulation pump is running continuously. 10.3.
10.3.5 offs Heating and cooling mode without season shut- Period P1: During this period, which in this example covers the period 1 October to 15 March, the following conditions apply: The diagram in the figure below, labelled Heating and cooling mode without season shut-offs, illustrates an operation example with the following setup: • • • Operating mode is set to heating and cooling, see section 8.9.
3. In case there is a brief period with either warmer or colder weather during this period, the system automatically turns on again. Turn-on conditions to cooling mode are explained in section 10.3.4 Cooling mode with winter-shut-off, page 48. Turn-on conditions to heating mode are explained in section 10.3.2 Heating mode with summer shut-off, page 47.
11 Trouble shooting The table below shows problems and alarms that can occur with the Climate Controller C-46 and descibes solutions. Alarms are indicated by a flashing alarm indicator and a warinig sign on the display. Problem Cause Actions Alarm: Missing sensor Sensor not defined in controller 1. Check in quick menu that the sensor is defined. Rerun the installation wizard if the sensor is missing. Wired sensor is not correctly connected 1. Check the sensor connection.
Problem Cause Actions The control oscillates Parameter setting is not ideal 1. Decrease both the Proportional coeff. and Integration time parameters, see section 8.9.2 Control response, page 32. 2. Check the pump. 3. Check the mixer valve and the supply temperature. The room temperature is too low The heat curve is not correct 1. Check the parameters T-slope and T-adjustment, see section 10.2 Adjusting the heat curve, page 46. The screen is blank. The Climate Controller C-46 has no power 1.
12 Technical data Climate Controller C-46 CE marking IP IP30 (IP: degree of inaccessibility to active parts of the product and degree of water) Degree of protection IK04 Low voltage tests EN 60730-1* and EN 60730-2-1** EMC (electromagnetic compatibility) tests EN 60730-1 and EN 301-489-3 ERM tests (electromagnetic EN 300 220-3 compatibility and radio spectrum matters) Antenna Home and building electronic systems (HBES) 50090-2-2 Part 2-2: System overview - General technical requirements Power
Installation report Climate Controller C-46 Sensors Thermostats Supply Return Outdoor Indoor H-56 T-75 T-54 T-55 Rooms #1 Floor sensor Mixing valve actuator Motorized Controller C-56 Radio Thermal #1 Pump Yes #2 #3 No 54 CLIMATE CONTROLLER C-46 - INSTALLATION AND OPERATION MANUAL
CLIMATE CONTROLLER C-46 - INSTALLATION AND OPERATION MANUAL 55
Uponor Housing Solutions Ltd. Snapethorpe House Tel. +44 1455 550 355 Rugby Road, Lutterworth Fax +44 1455 550 366 Leicestershire LE17 4HN www.uponorhousingsolutions.co.uk Uponor reserves the right to change specifications without prior notice, in keeping with our policy of continuous improvement and development.