Technical data

Section 5
Technical Data
SetPoint 501
Literature SetPoint 501 and 501s Controllers Installation
and Operation Manual
Control Microprocessor PI control; This is not a safety
(limit) control.
Packaged Weight 0.46 lb. (210 g), Enclosure J, white PVC plastic
Dimensions 2
7
8" H x 2
7
8" W x
13
16" D (73 x 73 x 21mm)
Approvals CSA C US, meets ICES and FCC regulations for
EMI/RFI
Ambient Conditions Indoor use only, -22 to 131°F (-30 to 55°C),
<90% RH non-condensing
Power Supply 24VAC ±10% 50/60 Hz 1 VA
Relay 24VAC, 2 A
13
Section 5 — Technical Data
SENS Shr
The optional sensor has a short circuit. Locate
and repair the problem as described in the
appropriate sensor instruction sheet. After
correcting the fault, press any button to clear
the error message. (See Figure 26.)
SENS OPN
The optional sensor has an open circuit. Locate
and repair the problem as described in the
appropriate sensor instruction sheet. After
correcting the fault, press any button to clear
the error message. (See Figure 27.)
12
Figure 28: SetPoint 501
Figure 26
Figure 27