Installation and Operation Manual

Customise user defined program for a full week
Note
This method resets the current user defined program to
factory defaults.
To customise the user defined program:
1. Press OK to enter parameter edit mode.
2. Use buttons - or + to select program U.
3. Press and hold OK until day 1 and 00:00 appears on the display.
4. Press OK to switch the marked interval between Comfort (
)
and ECO mode (
).
5. Use buttons - or + to move the marker (at the bottom of the
display). When moving the marker from one interval to another
save the selected mode to that interval.
6. Repeat steps 4 and 5 until the display shows 23:30.
7. Press + to finalize programming the current day.
The text Copy Yes appears (Yes is flashing).
8. Use buttons - or + to select Yes or No and press OK to confirm.
Yes: Copy the setting of the current day to the next. Repeat for
every day that should be identical.
No: Create a new scheduling interval for the following day. Then
repeat steps 4 through 8 until the whole week is programmed.
9. The display returns to the settings menu when the final day is
done.
02 Heating/cooling changeover
This menu is not visible if the thermostat is registered to a room
controller. Heating/cooling changeover will be controlled by a physical
heating/cooling switch or in the Uponor Smatrix PULSE app (requires
communication module).
03 ECO mode setback temperature
Default: 4 ˚C
Setting range: 0 – 11 ˚C, 0.5 ˚C increments
In this menu the setback temperature for whenever the channel is in
ECO mode is set.
The setting adjusts the current setpoint with the set value. In heating
mode the setpoint is reduced, and in cooling mode it is increased.
If the setback temperature is set to 0, the thermostat will remain
unaffected if a program sets the system in ECO mode.
This menu is not visible if a communication module is connected to
the system. The setting is then available in the Uponor Smatrix
PULSE app.
See Change settings, Page 90, for how to change the setting.
04 Control mode
In this menu control mode for the thermostat is set.
If an external sensor is connected to the thermostat, a control mode
must be chosen to accommodate the extra functionality of the sensor.
Current control mode is displayed (RT, RFT, RS or RO).
See Change settings, Page 90, for how to change the setting.
Uponor Smatrix Wave T-169
Symbol Description
Room temperature sensor
Room temperature sensor and floor temperature
sensor
Remote sensor
Room temperature sensor and outdoor temperature
sensor
05 High floor temperature limitation
Note
This parameter cannot be set lower than the set value in
settings menu 06 Low floor temperature limitation.
Default: 26 ˚C
Setting range: 20 – 35 ˚C, 0.5 ˚C increments
In this menu a limit on the maximum allowable floor temperature is
set.
This menu is only visible if control mode RFT is activated in settings
menu 04. For systems with a communication module this menu only
shows the set value, changes are done in the Uponor Smatrix
PULSE app.
See Change settings, Page 90, for how to change the setting.
06 Low floor temperature limitation
Note
This parameter cannot be set higher than the set value in
settings menu 05 High floor temperature limitation.
Default: 20 ˚C
Setting range: 10 – 30 ˚C, 0.5 ˚C increments
In this menu a limit on the minimum allowable floor temperature is
set.
This menu is only visible if control mode RFT is activated in settings
menu 04. For systems with a communication module this menu only
shows the set value, changes are done in the Uponor Smatrix
PULSE app.
See Change settings, Page 90, for how to change the setting.
Uponor Smatrix Wave PULSE
|
Installation and operation manual
|
64