Installation manual
Uponor Control System - Installation Manual 11
3.4.1 Mark room thermostats
3.4.2 Insert batteries
3.4.3 Register room thermostats
Example of registration: thermostat placed in a room, with
3 loops connected to channels 02 and 03.
• Type of batteries for the thermostats:
2x Alkaline AAA 1.5V. Respect the polarity.
• Mark the thermostats with the channel numbers
they are to control e.g. 02, 03. For a system
with an interface and several controllers the ID
of the controller has to be added e.g. 1.02,
1.03, 2.02, 2.03.
See: controller Operation Manual
Press the Test push-button
➜
The Test LED lights up .
Press the push-buttons of channels 02 and 03
➜
The LED of channels 02 and 03 flash .
1
2
3
Using a point, press the registration button of the
thermostat for at least 5 seconds.
For Thermostat Display T-75:
• The temperature is replaced by 2 lines
• When the temperature appears again the button
can be released
For Thermostat T-55 and Thermostat Public T-53:
• The LED of thermostat blinks one time only
➜
If registration is successful the LEDs of channels 02
and 03 switches on after 10 s
.
If channel registration fails (the channel LEDs
continues to flash or switch off), follow steps 2 to 4
once more.
Register all room thermostats
Press Test push-button to end the registration process
➜
The Test LED switch off
.
LED LED status
LED on
LED flash
LED off
To cancel registration of a channel and to reset the
controller: see: "3.9 Resetting", page: 17.
Wrong registration of the channels will cause bad
temperature control.
4
5