Installation manual

Uponor Control System - Installation Manual 9
Controller heating / cooling input
Should your system include a cooling unit, it is possible to
manage the Uponor Control System with the help of a
heating / cooling switch input.
The contact may be operated in different ways: timer,
ancillary control system, 2 position switch.
The heating / cooling input operates with the connection of a
dry contact.
When the contact of the relay is open, the system is in
heating mode.
When the contact of the relay is closed, the system is in
cooling mode.
Circulation pump relay
The Uponor Control System can operate a circulation pump
on heating/cooling demand. The controlled use of a
circulation pump improves the efficiency and responsiveness
of the underfloor heating.
Example of an installation:
The controller controls the circulation pump via connection on
terminal block (dry contact).
WARNING
Do not apply voltage to the controller heating /
cooling input. Damage to the Uponor Control
System will occur.
Heating / cooling relay
Heating / cooling contact
Controller heating / cooling input (potential free dry
contact)
Example of different type of heating / cooling relay
input
See the heating / cooling relay documentation.
1
2
3
4
WARNING
See the circulation pump supplier documentation
before performing the connection.
1
Ensure the power is disconnected
2
Open 230V compartment and fix cover to hanger
3
Connect "L" wire from/to pump via relay
4
Close 230V compartment
The electrical circuits of the pump must be
protected by a maximum 6A circuit-breaker.