INDOOR CLIMATE UPONOR CONTROL SYSTEM KNX INTERFACE MANUAL KNX Interface Manual Connecting Uponor Controller C-56 with Media Coupler TR131A/B 02 | 2011
Contents 1 Copyright and Disclaimer ............................ 3 2 Preface ........................................................... 4 2.1 Safety instructions ........................................... 4 2.2 Disposal ........................................................... 4 3 Description .................................................... 4 3.1 Overview.......................................................... 4 3.2 Target group...................................................
1 Copyright and Disclaimer Uponor has prepared this Uponor Control System Installation and Operation Manual and all the content included solely for information purposes. The contents of the Manual (including graphics, logos, icons, text, and images) are copyrighted and protected by worldwide copyright laws and treaty provisions. You agree to comply with all copyright laws worldwide in your use of the Manual.
2 Preface 3 The Uponor KNX Interface Manual describes how to set up the Uponor Controller C-56 and the Media Coupler TR131 to communicate on the KNX interface. 2.1 Safety instructions Warnings used in this manual The following symbols are used in the manual to indicate special precautions when installing and operating any Uponor equipment: Description 3.1 Overview The Uponor Controller C-56 Radio can be connected to a standard KNX bus via a Media Coupler TR131.
4 System setup 4.1 Uponor Controller C-56 Radio system setup There are two main options: • The Uponor Controllers C-56 Radio are grouped in up to three devices per system using the same Uponor Interface I-76. This means that the controllers are numbered and interconnected through the Uponor system bus. In ETS, each group will have one master Uponor Controller C-56 Radio that also stores the system data points for that group. The master will always be controller #1.
4.4 ETS handling of TR131 and Uponor Controller C-56 Radio 4.4.1 Addressing and synchronizing Uponor Controller C-56 Radio • The Media Coupler TR131 is given its physical address as with any normal KNX device on the wired bus • All other RF devices are given their physical addresses through the Media Coupler plug-in • For all RF devices except the Media Coupler: Always use the “RF-download” menu. The default “Download” menu will not work.
5 5.1 Uponor Controller C-56 Radio data point lists Data point list per zone Parameter name Explanation KNX data type Display condition Read Limited Full only write access access Room Temperature Info Measured room temperature. Can be supplied DPT_Value_Temp by Uponor Thermostats or other KNX devices. R R R/W Room Setpoint Local Info Local room setpoint. Can be set in Uponor thermostats or other KNX devices. DPT_Value_Temp R R R/W Remote Setpoint Remote room setpoint.
Parameter name Explanation KNX data type HVAC Mode DPT_HVACMode Current control mode: Comfort, ECO, or Frost protection Display condition Read Limited Full only write access access R R R Relative Humidity From wireless RH sensor DPT_Value_ Humidity Valid if RH sensor is R linked R R/W Tamper Alarm 0 = No alarm, 1 = Alarm DPT_Alarm Valid if T-54 is linked R R R Technical Alarm Option if Uponor Thermostat T-53 is used DPT_Alarm Valid if T-53 is linked R R R 5.
UPONOR CONTROL SYSTEM KNX INTERFACE MANUAL - CONNECTING UPONOR CONTROLLER C-56 WITH MEDIA COUPLER TR131A/B 9
Uponor Corporation P.O. Box 37 FI-01511 Vantaa Tel. +358 20 129 211 Fax +358 20 129 2841 www.uponor.com Uponor reserves the right to change specifications without prior notice, in keeping with our policy of continuous improvement and development.