User Manual

To set the shooting time, after opening the cylinders compartment door,
at the top of the PCB, facing the board you must move the jumper P3
in “setting” position.
Then, holding down the button S1 “SET”, 6 leds on the front will flash and
each flash is equivalent to one second.
If you press the button again, the shooting time is not added to the one
previously set, but will restart from zero.
12
SHOOTING TIME SETTING AND FOG FLOW DIRECTION
SET
RESET TAMPER
P3
SET TIME SHOOTS
The following tables indicate the suggested fog emission in relation to the number of seconds of shooting set in average
condition of temperature, air pressure and humidity.
TABLE RECOMMENDED FOR SHOOTING BASED ON M³ TO PROTECT
Fogging systems URFog FAST 03 and FAST 02 are able to produce fog for a maximum respectively of 15 and 25 seconds
per single shoot. The maximum quantity of 9,7 ml/s (FAST03) and 12,8 ml/s (FAST 02) allows to fill an area of about 200
and 400 m
3
.
There might be cases in which, due to specific characteristic of the location, nozzle type, levels of temperature and air
pressure, degree of the fog density and light in the target area, the shooting time can be increased or decreased. For
example, above 5 m of height the shooting time must be integrated and above 7 m, every additional meter should be
considered as double.
N.B. Before opening side door ensure that the control panel is set to “service”, so that the opening of the
circuit “anti-sabotage or tamper” does not cause any shooting.
HxLxP-------- Height x Width x Depth of the area to protect
D------------- Density of the produced fog
V------------- Temperature and air pressure
R------------- Acceptable residue in case of saturation of V parameter
I-------------- Intensity of the surface light
(HxLxP) x D x V x R x I
The machines are programmed to activate the internal pump to verify any possible
obstruction to the nozzle in the following conditions: arming, cylinder reset and shot.
The duration of this process is about 15 minutes (verifiable by a light buzz)
at the end of which no action is required as the pump will cease autonomously.
12