RESET FROM FAULT CONDITION
This process is useful to discriminate false interpretations of faults caused by electrical shocks or serious problems on
power supply from thermal loop problems.
1) Serious fault signal occurs with a first phase when the buzzer emits a continuous sound for 20 minutes and blue led
flashes, the output FAULT immediately switch (if the generator is disconnected and connected again you can go directly at
point 3)
2) After 20 minutes, the buzzer stops, while blue led goes on flashing, the FAULT output remains closed.
This phase remains permanently, until the machine is completely disarmed.
3) When you connect again the machine, blue and red leds flash alternately and any sound is emitted.
This phase lasts for 30 minutes, then, the output FAULT is reset and the generator start to work again.
If during this process the generator is disconnected, when you connect it again the time start again from the beginning and
for 30 minutes.
If at the end of this process, the generator start to work again regularly is not necessary any further operation.
If occurs again the fault condition within the following 20 minutes, it’s necessary a check from the assistance center, or to
send the machine back to the factory.