Installation Guide

-10-
Operation Of The Heater
1. Burn wood or wood products only. The wood should be well
seasons prior to use for maximum efciency.
2. Provide air into the room for combustion.
3. Do Not touch the heater after ring until it has cooled.
4. Do Not use a grate or elevate re, build re directly on hearth.
The fuel feed door must remain closed during operation.
Chimney Connection
MASONRY CHIMNEY
The masonry chimney must comply with UL, ULC codes. Before
using an existing masonry chimney, clean the chimney and inspect
the ue liner to be sure it is safe to use. Make repairs before attaching
the heater. See Page 3, Item 5. Look at Fig. 5. The connector pipe
and ttings you will need to connect directly to a masonry chimney
are shown. If the connector pipe must go through a combustible wall
before entering the masonry chimney, consult a qualied mason or
chimney dealer. The installation must conform to local re codes, and
NFPA 211(USA) or CAN/CSA-B365-M91(CANADA). Do not connect this
heater into the same chimney ue as the replace or ue from another
heater. The chimney used for a heater must not be used to ventilate
the cellar or basement. If there is a cleanout opening at the base of
the chimney, close it tightly.
UL/ULC LISTED CHIMNEY
Carefully follow chimney manufacturer's instructions. Use only listed
type HT per UL, ULC 103, 6-in diameter black or blued chimney con-
nector, minimum 24 gauge steel. If your chimney starts at the ceiling
(Fig. 6), you will need enough 6" pipe to reach the ceiling.
The top of the chimney must be at least 3 feet above the roof and
be at least 2 feet higher than any point of the roof within 10 feet. (Fig 6).
Use double or triple wall pipe for the exterior portion of the chimney.
RULES FOR CONNECTOR PIPE INSTALLATION
1. Crimped end of the pipe must be installed toward the heater.
The pipe should slide into the ue collar. The pipe should be
rmly attached to the ue collar with 3 screws and sealed with
furnace cement.
2. Slope any horizontal pipe upward toward the chimney at least
1/4 inch for each foot of horizontal run. Horizontal section must
be a minimum of 24" from stove.
3. You must have at least 18" inches clearance between any hori-
zontal piping and the ceiling.
4. The pipe cannot extend into the chimney ue.(Fig. 7)
5. Seal each connector pipe joint with furnace cement. Also, seal
the pipe at the chimney. Seal the inside with high temperature
silicone and the outside with high temperature tape.
6. Use 3 sheet metal screws at each joint to make the piping rigid.
7. It is recommended that no more than two (2) 90 degree bends
be used in the stove pipe installation as more than two (2) may
decrease the amount of draw and possibly cause smoke spillage.
NOTE: The chimney connector shall not pass through an
attic, roof space, oor, ceiling, or similar concealed space.
Where passage through a wall or partition of combustible
construction is desired, the installation must conform with
CAN/CSA - B365.
FIG. 5
ELBOW
COLLAR
THIMBLE
FLOOR PROTECTOR
FLUE CONNECTION-NON-COMBUSTIBLE WALL
PIPE
NONCOMBUSTIBLE WALL
PIPE
BAROMETRIC
DRAFT REGULATOR
WRONG
RIGHT
FIG. 6
FIG. 5
ELBOW
COLLAR
THIMBLE
PIPE REDUCER
FLOOR PROTECTOR
FLOOR PROTECTOR
3 FT. MIN.
2 FT. MIN
10 FT.
CHIMNEY CAP MANDATORY
11 FT. MINIMUM
FIG. 7
WRONG
FLUE CONNECTION-NON-COMBUSTIBLE WALL
PIPE
NONCOMBUSTIBLE WALL
PIPE
BAROMETRIC
DRAFT REGULATOR
BAROMETRIC
DRAFT REGULATOR
PIPE
NONCOMBUSTIBLE
CONSTRUCTION IN
ACCORDANCE WITH
NFPA 211
WRONG
RIGHT
FIG. 6
FIG. 5
ELBOW
COLLAR
THIMBLE
PIPE REDUCER
FLOOR PROTECTOR
FLOOR PROTECTOR
3 FT. MIN.
2 FT. MIN
10 FT.
CHIMNEY CAP MANDATORY
11 FT. MINIMUM
FIG. 7
WRONG
FLUE CONNECTION-NON-COMBUSTIBLE WALL
PIPE
NONCOMBUSTIBLE WALL
PIPE
BAROMETRIC
DRAFT REGULATOR
BAROMETRIC
DRAFT REGULATOR
PIPE
NONCOMBUSTIBLE
CONSTRUCTION IN
ACCORDANCE WITH
NFPA 211