Installation Guide
-8-
Installation
Place the heater on solid masonry or solid concrete. When the heater is used on a combustible oor, use
an Underwriters Listed oor protector. The oor protector must comply with UL Standards (USA) and CAN/ULC
(Canada) and have an R-value of 2.06. The oor protector needs to extend at least 16" beyond the door side
of the heater and 8" to each side. It should also extend 8" beyond the rear for Canada. The oor protector
needs to extend 2" beyond each side of the ue pipe if it is elbowed towards a wall as well as 2" on each side
of the ue for horizontal runs.
1. After consulting the installation instructions for minimum clearances to combustibles, locate your oor
protector accordingly and carefully place the stove in your selected location. Install stove pipe, elbows
and thimble as necessary, utilizing either a recently cleaned and inspected masonry chimney (properly
lined) or a UL, ULC Listed chimney. Insure that the xed ue bafe that is provided is installed in the ue
collar. This bafe is intended to be in a xed location for optimal combustion. Do not remove or alter the
location of this bafe. It is against federal regulations and will void your warranty.
2. Again, check the following illustrations and be sure you have the clearances shown from the heater and
the connector pipe to combustible surfaces. If you have a solid brick or stone wall behind your heater,
please consult your local building code for specic regulations that may apply in your area. However, if
the wall is only faced with brick or stone, consider it a combustible wall. To reduce ue clearances from
combustible materials, contact your local safety department.
3. If your chimney drafts excessively, purchase and use a Barometric Draft Regulator (DR6 available from
factory).
4. The chimney connection should be as short as possible, and the heater must have its own ue. Do not
connect this unit to a chimney ue serving other appliances.
MINIMUM CLEARANCE
TO COMBUSTIBLE WALLS
US, CANADA
HEATER/FLOOR PROTECTOR LOCATION
(Dimensions are required for non-protected surfaces. See
chart for dimensions for protected surfaces.)
419mm
18”
419mm
18”