User's Manual
GE AccessSmart 313 Last Update July 6, 2005
37
9.3.1 EVENT MEMORY
9.3.2 ID DISPLAY
☞. You can select whether you will use event memory or not. When you select USE and in case of an event
memory, GE313 generates an error message and keeps all events stored in the memory. When you select
UNUSE, GE313 will not generate an error and new event overwrite into the event buffers. If you use GE313
for standalone (just for door access), select UNUSE.
☞. This function is to set display mode. If you want to display user ID number on the LCD, select
ID+MESSAGE. MESSAGE: Text message and “********” characters will be displayed on the LCD and it
will not display user ID number. ID+MESSAGE: The user ID number will be displayed on the LCD with text
message. Default setting is MESSAGE only.
GE AccessSmart 313 Last Update July 6, 2005
38
9.3.3 TIME UNIT SETTING
9.3.4 OUTPUT T/S+ID
. ☞ This menu is to define time unit for 5 output ports.
1sec: Output Time will be calculated by one second time unit for in/out definition.
0.1sec: Output Time will be calculated by 1/10 second time unit (100ms) for in/out definition
Ex) If you want to activate Door Relay (Relay #1, DR) for 3 second, you have to set as follow.
- Set Output Time Unit to 1 SEC.
- Set Door Relay (DR) Output Time to “03”
Ex) ) If you want to activate Door Relay (Relay #1, DR) for 0.5 second, you have to set as follow.
- Set Output Time Unit to 0.1 SEC.
- Set Door Relay (DR) Output Time to “05”
☞. Output Time Schedule+ID is to unlock the door when the first user grants the access during the Time Interval
of the Time Schedule. The door will be locked just after the Time Interval period is over.
UNUSE: Door will unlock at the beginning of the Time Interval of the Time Schedule code.
USE: Door will unlock when the first user grants the access during the Time Interval of the Time Schedule.