9.3.5 ANTI-PASS BACK MODE
9.3.6 DURESS MODE
9.3.7 WIEGAND OUTPUT
. You can set Duress Mode for Reader#1. Default setting is UNUSE. If you select USE, LCD will display
default Duress Password ‘00’. Enter 2 digit Duress Password.
Note!!
If you are in Duress condition, enter 2 digit Duress Password and press <ENT> key prior to present the card.
Door will be opened as normal but the Duress Alarm will be generated and reported to the host PC.
. The Anti-pass Back mode is only used when you installed Exit Reader. Do not set this mode in USE when
you installed Exit Button. You must install GE313 for entry and Exit Reader for Exit.
UNUSE: Anti-pass Back mode OFF
USE: Anti-pass Back mode ON
. ALL FLAG RESET: Allow the access only one time whatever the Anti-pass Back flag is.
GE AccessSmart 313 Last Update July 6, 2005
40
9.3.8 DOOR OPEN ALARM TIME SETTING
. When the door is not closed after the door open time is over, you may set the delay time to generate Door
Open Alarm. To use this function, you have to install a Door Contact Sensor on the door and setup the alarm
time by Door Contact Sensor. ‘03’ sec. is default time.
00: Alarm if the door is not closed after the door open time (Door Relay time).
01~98: Alarm if the door is not closed after the door open time and over the alarm delay time. (01~98s)
99: No Door O
p
en Alar
m
. This is the function to use GE313 as a Reader and sends 26bit Wiegand Output through two TTL output ports.
Press <ENT> key and select USE by pressing <4> or <6> key then press <ENT> key for setting.
UNUSE: Normal TTL outputs will be activated.
USE: 26bit Wiegand output will be generated through TTL1 and TTL2 port.
When an unregistered card is read, the “CARD SCCANNING OK” message will appear on the LCD.
z TTL1 : Data 0 TTL2 : Data 1