9.3.3 TIME UNIT SETTING
9.3.4 OUTPUT T/S+ID
. ☞ This menu is to define time unit for 5 output ports.
1sec: Output Time will be calculated by one second time unit for in/out definition.
0.1sec: Output Time will be calculated by 1/10 second time unit (100ms) for in/out definition
Ex) If you want to activate Door Relay (Relay #1, DR) for 3 second, you have to set as follow.
- Set Output Time Unit to 1 SEC.
- Set Door Relay (DR) Output Time to “03”
Ex) ) If you want to activate Door Relay (Relay #1, DR) for 0.5 second, you have to set as follow.
- Set Output Time Unit to 0.1 SEC.
- Set Door Relay (DR) Output Time to “05”
☞. Output Time Schedule+ID is to unlock the door when the first user grants the access during the Time Interval
of the Time Schedule. The door will be locked just after the Time Interval period is over.
UNUSE: Door will unlock at the beginning of the Time Interval of the Time Schedule code.
USE: Door will unlock when the first user grants the access during the Time Interval of the Time Schedule.
GE AccessSmart 314 Last Update July 6, 2005
40
9.3.5 ANTI-PASS BACK MODE
9.3.6 DURESS MODE
9.3.7 WIEGAND OUTPUT
☞. You can set Duress Mode for Reader#1. Default setting is UNUSE. If you select USE, LCD will display
default Duress Password ‘00’. Enter 2 digit Duress Password.
Note!!
If you are in Duress condition, enter 2 digit Duress Password and press <ENT> key prior to present the card.
Door will be opened as normal but the Duress Alarm will be generated and reported to the host PC.
☞. The Anti-pass Back mode is only used when you installed Exit Reader. Do not set this mode in USE when
you installed Exit Button. You must install GE314 for entry and Exit Reader for Exit.
UNUSE: Anti-pass Back mode OFF
USE: Anti-pass Back mode ON
☞. ALL FLAG RESET: Allow the access only one time whatever the Anti-pass Back flag is.