☞ “SCHEDULE ERROR” message shows when RFID card is read.
Cause Error in RFID card registration, time schedule setting or the system itself.
Solution 1. If it was a properly operating unit before, there has been an electric shock that damaged the internal
memory and data. Please initialize the unit as instructed in the manual.
2. Check if ID information has been put in incorrectly during its registration.
* Register ID again checking the following points.
-In order to restrict access of the ID user for specific time zone as instructed in the manual, register time
schedule in advance and apply the time schedule code(1~10) in the registration of the user ID.
- In order to allow the user to access at all times, put in “00”.
3. Use software for time schedule setting in case it is connected to PC as the software manual.
4. If the trouble remains after checking the above, contact a designated service center.
☞ “ACCESS DOOR ERR” message shows when the RF ID card is read.
Cause Incorrect user setting or false of internal circuit.
Solution 1. If it was a properly operating unit before, there has been an electric shock that damaged the internal
memory and data. Please initialize the unit as instructed in the manual.
2. Check if ID information has been put in incorrectly during its registration.
* Register ID again and check the following points:
- Since the controller has two reader ports, define “RD” – door for the user to be allowed to access
(Reader1(Bilt-in reader) only: “1”, Reader 2(Extra reader) only: “2”, Reader 1 & 2 both: “0 or 3”)
- If RD is set as “1”, only when the card is read at Reader 1, the door opens but not at Reader2. If it is
read at Reader 2, “ACCESS DOOR ERROR” message shows up.
- If RD is set as “2”, only when the card is read at reader 2, the door opens but not at reader1. If it is read
at reader 1, “ACCESS DOOR ERROR” message shows up.
- If RD is set as “0 or 3”, reader 1 & 2 both open each door.
3. If the trouble remains after checking the above, contact a designated service center.
GE AccessSmart 314 Last Update July 6, 2005
66
☞ The controller does not communicate with the Host-PC.
Cause A defective cable is used, errors in wiring, an error in setting COMM ID of the controller, or damage on
the communication port (either on PC side or on the controller side).
Solution 1. Please check the settings of the application S/W and the controller.
- Check if the controller’s COMM ID is listed on the application S/W.
- Set the different COMM ID when two or more controllers are installed.
- Check if the communication speed (9600bps default) is the same as the setting on the S/W.
- Make sure that the PC’s COM port is set correctly on the S/W.
- The parameters at the S/W should be set as following:
Parity bit : NONE
Data bit : 8bit
Stop bit : 1bit
2. Check the line connection for communication.
RS232 RS485 (mono)
GE313 PC GE314
RS485/232
Converter
PC
RX TX RTX(-) RTX(-)
TX RX RTX(+) RTX(+)
GND GND
The RS232 cable from
the converter
RS485(Multi Drop)
GE314 GE314
RS485/232
Converter
PC
RX(-) RX(-) TX(-)
RX(+) RX(+) TX(+)
The RS232 cable from
the converter
3. In case of setting RS485 communication, we recommend to use line-end resistors of 120 Ohm
between the RTX (+) and RTX (-) lines. Apply the same resistors to the converter RS485 lines.
Consult a service center or an electric technician if you are not sure how to do it.
4. When a multi-drop communication doesn’t work, test one-by-one communication first.
5. If the trouble remains after the procedure above, contact a designated service center.