Installation Instructions

7
AL-111X Arming Station
Offline Mode
If the RAS has power available but loses communications with the panel, the RAS will go into offline mode. In this mode,
all LEDs will flash at the slow rate and the LCD will display “-System Fault-”. This condition may be caused by the
following:
RAS is set to an address that is not polled by the panel or 4-door controller DGP.
The D+ or D- wire is dissconnected.
Unused Keys
There are four keys on the keypad reserved for future use. The unused keys are circled in the following illustration.
Text Scrolling Speed
The text scrolling speed may be changed (for all the LCD RAS in the system) in the Alliance Installer Menu, System
Options 19.7 (LCD Rotation Display option). Refer to the Alliance programming manual for details.
Troubleshooting
No LED or LCD display:
Verify the +12 and 0V wire connections on both the RAS and the power supply.
Verify power output on the DGP or external power supply.
Area and Status LEDs are flashing and the LCD display reads, “-System Fault-”:
Verify the D+ and D- wire connections (they may be reversed or open circuit).
Verify that the address DIP switches of the RAS are set to the proper address.
Verity that the control panel or 4-door controller DGP is polling the RAS address.
An AL-1115 or AL-1116 RAS with Smart Card reader does not respond to a Smart Card:
The RAS may actually be an AL-1110 or AL-1111 type that is not fitted with a Smart Card reader.
The RAS may not be programmed correctly. See Programming.
The Smart Card may not be programmed (may be blank).
This device complies with Part 15 of the FCC rules. Operation is subject to the following conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, including interference that may cause undesired operation.
3. Changes or modifications not expressly approved by the party responsible for compliance could void the user’s
authority to operate the equipment.
FCC Compliance for AL-1110/AL-1111