Operation and Installation Manual
18
Thermostat Installation
1. 
Thermostat should be installed on inside wall about 
four feet above the oor.
2. 
NEVER install thermostat on outside wall.
3. 
Do not install thermostat where it will be affected by:
• Drafts
• Hot or cold pipes
• Sun light
• Lighting xtures
• Television sets
• Fireplace or chimney
4. 
Check thermostat operation by raising and lowering 
thermostat as required to start and stop burner.
5. 
Instructions for nal adjustment of thermostat 
are packaged with thermostat ( adjusting heating 
anticipator, calibration, ect.).
Electrically bond boiler to ground in accordance with 
requirements of authority having jurisdiction. Refer to:
• USA- National Electrical Code, ANSI/NFPA 70.
Install fused disconnect switch between boiler and meter at 
convenient location.
Sequence Of Operations
On call for heat, thermostat will actuate, completing 
circuit to limit. In turn, circulator and ignition systems are 
activated and ignition will begin.
In event boiler water temperature exceeds high limit 
setting on boiler mounted limit, power will be interrupted 
between limit and ignition system. Power will remain off 
until boiler water temperature drops below high limit 
setting. Circulator will continue to operate under this 
condition until thermostat is satised.
ELECTRICAL WIRING
WARNING
Electrical shock hazard. Turn OFF electrical power supply 
at service panel before making electrical connections. 
Failure to do so could result in death or serious injury.
! 