Operation and Installation Manual
23
Operating Instructions
1. 
Inspect venting system at start of each heating season. 
2. 
Check vent pipe from boiler to chimney for signs 
of deterioration by rust or sagging joints. Repair if 
necessary. 
3. 
Remove vent pipe at base of chimney or ue and, using 
mirror, check for obstruction.
Safety Relief Valve
 WARNING
Burn and scald hazard. Safety relief valve could     
discharge steam or hot water during operation. 
! 
• Operate lever of safety relief valve, on boiler 
periodically to make sure it is functioning properly. 
• Safety relief valve should open before water pressure 
exceeds 30 psi reading on gauge. 
• If this pressure is exceeded and safety relief valve 
starts leaking water when boiler is operating at normal 
pressures, it should be immediately replaced. 
• Corrosion can build up rapidly at valve seat and 
prevent its functioning as safety device. See Figure 
#11, page 13.
Start-Up And Adjustment Of Oil Burner 
(See oil burner instructions for nozzle and electrode 
setting)
A.  Check oil burner nozzle to verify it is tight in the 
adapter. 
B.  Check electrode setting, may have been jarred out 
of position during transportation.
C.  Burner mounting bolts should be tight.
D.  Set room thermostat to call for heat, or jump 
thermostat contacts on the boiler control.
E.  Open all oil line valves.
F.  Turn service switch on. Burner should start.
G.  On one pipe fuel systems only, vent pump as soon 
as burner starts. Allow oil to run until all traces of 
air in the suction line disappear.
H.  Turn “OFF” burner and install pressure gauge port 
on pump.
I.  Start burner again and check oil pressure per setup 
charts on page 24. Adjust if necessary.
Do not set re visually. 
Instruments are only reliable 
method to determine proper air adjustments. 
Improperly adjusted burner causes soot and high fuel bills 
because of incomplete combustion of fuel oil. This in turn 
may require excessive boiler maintenance, service costs, 
and in some instances, house cleaning or redecorating. A 
competent service mechanic should be consulted to make 
proper adjustments with smoke tester, CO
2
 indicator and 
draft gauge. 
Instructions For Proper Operation Of Boiler 
Burner Unit
A ¼” diameter slot is provided in inspection cover plate to 
take draft readings in combustion chamber. See Figure 
#26. A ¼” diameter hole will be required in ue pipe 
between boiler and barometric damper (if used) to take 
draft, CO
2
, smoke and temperature readings. Adjust air 
shutter on oil burner to obtain “trace” of smoke. Measure 
CO
2
 at this point. Increase air adjustment to lower CO
2
approximately one (1) percent. Check to insure minimum 
negative .02” w.c., (water column), “overre” draft and 
zero (0) smoke. If - .02”w.c. “overre” draft can not be 
maintained, changes and/or modications may be required 
in venting or chimney.
Following tables (page 25) are provided as guideline for 
initial start-up. Final adjustments MUST be made using 
combustion instruments as previously mentioned.
Check Safety Control Circuit - for satisfactory 
performance after burner adjustments have been made.
1. 
High limit control: remove cover and note temperature 
setting. See Figure #26. With burner operating, 
decrease setting to minimum point. When boiler water 
temperature exceeds this set point, high limit switch 
will open, shutting off power to oil burner. Return 
setting to desired high limit point. Burner should 
restart. Refer to instructions included with limit.
2. 
Primary control and ame sensor check following: 
A.  Flame failure - simulate by shutting off oil supply 
with hand valve while burner is on. After ame 
extinguishes, control goes through recycle period 
and attempts another ignition then locks out.
To restart, open oil supply valve and reset safety 
switch. Refer to instructions included with burner.
B.  Ignition failure - with burner off, close oil supply 
valve and run through start-up procedure, The 
safety switch should lock out as in ame failure.
C.  Power failure - Turn off main power supply switch 
while burner is operating. When burner stops, 
restore power and burner should start.
If operation is not as described as above, check 
wiring and controls.
OPERATING INSTRUCTIONS










