Operation and Installation Manual
9
1. 
Connect supply and return piping as suggested in 
Figure #5, below. When boiler is used in connection 
with refrigerated systems:
A.  Chilled medium MUST BE IN PARALLEL with boiler.
B.  Use appropriate valves to prevent chilled medium 
from entering heating boiler.
2. 
During heating cycle open valves A and B, close valves 
C and D.
3. 
During heating cooling cycle open valves C and D, close 
valves A and B.
A.  Maintain minimum clearance of one inch to hot 
water pipes.
In air handling units where they may be exposed to 
refrigerated air circulation, boiler piping system MUST be 
supplied with ow control valves or other automatic means 
to prevent gravity circulation of boiler water during cooling 
cycle.
4. 
Hot water boilers installed above radiation level must 
be provided with low water device either as part of 
boiler or at time of boiler installation.
5. 
When boiler is connected to heating system utilizing 
multiple zoned circulators, each circulator must be 
supplied with ow control valve to prevent gravity 
circulation.
* Reduced pressure back ow preventer must be used 
under provisions required by the Environmental 
Protection Agency, (EPA).
6. 
Bypass piping is an option which gives ability to 
adjust supply boiler water temperature to t system 
or condition of installation. Although, this method of 
piping is not typically required for baseboard heating 
systems.
CONNECTING SUPPLY AND RETURN PIPING
Figure #5 Typical Piping Conguration