Installation Guide
9d
5
INSTALLATION INSTRUCTIONS
flow. This check valve is mandatory when sharing a discharge line with
another pump (i.e. a back-up pump or a second primary pump).
(a)
When a check valve is used, a 1/8 in. air bleed hole must be drilled in
the PVC pipe above the pump. Drill the hole at a 45° angle toward
the bottom of the sump to avoid splashing water outside the sump
pit. Make sure the hole is above the water line and below the check
valve. If a hole is not drilled above the pump, an air lock may prevent
the pump from operating.
7. Install a gate valve or ball valve if required by any codes.
8. The horizontal discharge pipe must be positioned in a downward
slope so any remaining water will drain away. Failure to do this will prevent
water from exiting the pit and damage the pump if the line freezes.
9. If you are replacing an old sump pump:
(a) Unplug the pump from the outlet.
(b) Loosen the check valve or rubber union by unscrewing the bottom hose
clamp. (If the existing system is installed without a check valve or rubber
union, saw the pipe apart above the sump pit.)
(c) Remove the old pump and unscrew the pipe and adapter.
(d) If the adapter fits into the new pump, screw the pipe into the pump. If
not, cut a piece of rigid PVC pipe and connect it to the new adapter by
cleaning and cementing the two pieces together. (Follow the instructions
on the PVC cleaner and cement.)
(e) Loosen the enclosed hose clamp by turning the screw counterclockwise
and slip it over the pipe on top of the pump.
(f) Hold the float switch against the discharge pipe so the cage is below the
bracket.
(g) Position the bottom of the float at the height you want the pump to
activate and turn the screw clockwise to tighten the hose clamp, but do
not tighten it completely at this time.
(h) Lower the pump into the sump by the handle.
(i) To avoid debris pouring into the float, it should be positioned on the side
of the discharge pipe opposite the drain tile. Note: It is desirable to
mount the float below the drain tile that empties into the pit. Mounting it
above the drain tile would allow water to fill the drain tile before the pump
is activated. (See diagram on page 4).
(j) Once the switch is in the desired position, tighten the hose clamp.
(k) Connect the pipe on the pump to the existing discharge pipe with a
rubber union or check valve and tighten the hose clamps securely.
9b
6a
9c
9f