emission condenser Peltronic Manual
Table Of Contents
- Part I
- Reset / Language selection
- Safety information!
- Technical data
- Use and operation
- Installing a pump in a vacuum system
- Notes regarding the (dry) ice condenser
- Notes concerning the operation of the inlet condenser IK
- Notes concerning the operation of the Peltronic emission condenser
- Notes concerning the operation of pumping units with silencer
- During operation
- Important notes regarding the use of gas ballast
- Important notes concerning the operation of the exhaust waste vapor condenser
- Shutdown & storage
- CVC 3000 Vacuum controller
- Menu guide
- Pump down function
- Vac Control function
- Auto mode
- Program function
- VACUULAN function
- Application examples
- Configuration
- Part II
- Readjustment of CVC 3000
- Calibration in the factory
- Cleaning the pressure transducer
- Interface parameters
- Accessories
- Troubleshooting
- Replacing diaphragms and valves
- Cleaning and inspecting the pump heads
- Disassembling the housing cover at the side of the emission condenser
- Replacing the diaphragm
- Assembling the housing cover at the side of the emission condenser
- Disassembling the housing cover at the side of the ON/OFF switch
- Assembling the housing cover at the side of the ON/OFF switch
- Assembling the fittings
- Cleaning and replacing components
- Notes on return to the factory
- Warranty
- Health and safety clearance form
- EC Declaration of Conformity of the Machinery
page 22 of 120
PC 3001 TE VARIO
pro
:
• Comply with all applicable safety measures and re-
quirements when using cryogenic coolants (e.g., dry
ice).
Attention: Coolant media may cause severe frostbite
when coming in contact with skin!
• Prior to every use: Inspect the condenser for faults.
There must be no damage on the glass surface. Do
not use damaged components.
• Use only transport receptacles intended for coolants.
• Wear safety glasses and protective gloves.
• Do not clamp the covers of condensers or coolant re-
ceptacles. Allow pressure equalization between cool-
ant and atmosphere.
Prevent the backpressure of gases and the backow of
condensates at the outlet.
Check the liquid level in the catchpots regularly and drain
condensate in time to prevent overlling. Install a level
sensor (see „Accessories“, pg. 94) for monitoring, if
necessary.
Provide appropriate protective measures to allow for the
possibility of failure and malfunction. The protective mea-
sures must also allow for the requirements of the respec-
tive application.
The CVC 3000 controller is powered by a short-circuit-
proof wide-range power supply with integrated overload
protection.
A temperature sensor at the circuit board protects the mo-
tor: Current limitation in case the temperature at the circuit
board raises above 158°F (70°C). At temperatures above
185°F (85°C) the pump is switched off. In case of a motor
blockage (after 10 start-up attempts) the pump is switched
off.
Note: Only manual reset is possible. Disconnect the pump
from the power source. Identify and eliminate the cause of
failure.
NOTICE