Installation Instructions

Gas supply adjustments (Commissioning Part II) 7
Instructions for installation and servicing aquaPLUS VUI 362-7 27
7.4 Adjusting the ignition rate
Undo screw and remove the cap (1).
Disconnect the modulating coil wires from the gas
valve, set the DHW temperature control to maximum
and fire the boiler at full rate by fully opening a hot
water tap.
Turn off the boiler at the main ON/OFF control.
Press and hold the "+" button, while pressing the
button turn the main ON/OFF control to the "1" ON
position.
Continue holding "+" button until display alternates
between "P1, P2, P3, P11, P12 and P13". Release "+"
button.
Press "+" button until "P2" (ignition rate) is shown in
display.
Press "i" button to operate boiler at full gas rate.
Use a suitably sized screwdriver to turn the inner
screw (2).
-Turn the screw (2) clockwise to increase the ignation
rate
- Turn the screw (2) anticlockwise to decrease the
ignation rate
Adjust the burner pressure until it matches the
ignition rate in table 7.7, page 30.
Turn off the hot water tap and reconnect the wires to
the modulating regulator.
To cancel selected "P1" or "P2" mode press the "i" and
"+" buttons simultaneously.
Warning!
The main burner pressure must be rechecked
after adjusting the ignition rate.
Refit cap (1) and replace screw. Re-check ignition and
main burner pressures. After completion of these tests
tighten the sealing screw and check all joints and test
points for soundness.
Fig. 7.4: Adjusting the ignition gas quantity
2
1
I