Technical data
10 Installation and maintenance manual atmoCRAFT
4.2 Dimensions
1
2
3
64
690
665
565
320
Ød
b
c
1100
1145
a
4
4
min. 100
100
690
4
Fig. 4.1 Dimensions for VK in mm
Key:
1 Heating feed
2 Gas connection
3 Heating return
4 Flue gas connection
Boiler Type A B C
∅ d
Heating feed/
Heating return
Gas connection
65 kW 850 860 960 180 R 1 1/2 R 1
75 kW 930 850 960 200 R 1 1/2 R 1
85 kW 1010 850 960 200 R 1 1/2 R 1
105 kW 1170 838 960 225 R 1 1/2 R 1
115 kW 1250 838 960 225 R 1 1/2 R 1
130 kW 1410 825 960 250 R 1 1/2 R 1 1/4
150 kW 1570 825 960 250 R 1 1/2 R 1 1/4
165 kW 1730 852 1012 300 R 1 1/2 R 1 1/4
Table 4.1 Dimensions (measurements in mm)
4 Assembly