Operation Manual
21Installation instructions – auroMATIC 560 0020008427_01
Display Turn the dial to adjust Setting range Factory setting
Setting the activation difference for
cylinder 1
(The activation difference should always be 2
K greater than the deactivation difference)
2 – 25 K 7 K
Setting the deactivation difference for cylin-
der 1
(The deactivation difference should always
be 2 K less than the activation difference)
1 – 20 K 3 K
Setting the max. temperature for cylinder 2 20 - 90 °C 60 °C
Table 6.1 System parameters (continued)
a
Caution!
The maximum permissible temperature of the
cylinder used (MAXT 2) must not be exceeded.
Display Turn the dial to adjust Setting range Factory setting
Setting the activation difference for
cylinder 2
(The activation difference should always
be 2 K greater than the deactivation differ-
ence)
2 – 25 K 7 K
Setting the deactivation difference for cylin-
der 2
(The deactivation difference should always
be 2 K less than the activation difference)
1 – 20 K 3 K
PRIO
Cylinder with highest priority
1, 2 1
FROS:
Frost protection function
-5 °C – 10 °C; OFF OFF
Table 6.1 System parameters (continued)
Start-up 6