Operation Manual

23Installation instructions – auroMATIC 560 0020008427_01
6.2 Resetting the system parameters to the de-
fault setting
You can restore the default settings for system parame-
ters and timer programs by pressing the programming
button "P" for roughly ten seconds. Then the display
flashes three times and all of the parameters are reset
to the factory defaults.
7 Service/diagnostics
You can access the service/diagnostics level by pressing
the programming button "P" and the dial simultaneously
(for roughly 3 seconds).
Display Actuators/sensor values Test procedure
Collector pump 1 test Collector pump 1 on, all other actuators off
Collector pump 2 test or circulation pump test (for hydrau-
lic plan 1)
Collector pump 2 on, all other actuators off
Diverter valve test Diverter valve on, all other actuators off
Anti-Legionnaires‘ pump test Anti-Legionnaires‘ pump on, all other actuators
off
Electrical heating rod (EP) test Electrical heating rod (EP) test on, all other actua-
tors off
C1/C2 contact test C1/C2 contact closed, all other actuators off
Table 7.1 Actuators and sensors
Start-up 6
Service/diagnostics 7