Operation Manual
Installation instructions – auroMATIC 560 0020008427_0126
10 Sensor characteristics
VR 10 standard sensor, type NTC 2.7 K
Sensor values Resistance value
0 °C 9191 Ohm
5 °C 7064 Ohm
10 °C 5214 Ohm
20 °C 3384 Ohm
25 °C 2692 Ohm
30 °C 2158 Ohm
40 °C 1416 Ohm
50 °C 954 Ohm
60 °C 658 Ohm
70 °C 463 Ohm
80 °C 333 Ohm
120 °C 105 Ohm
Table 10.1 Characteristics of VR 10 standard sensor
VR 11 standard sensor, type NTC 10 K
Sensor values Resistance value
-20 °C 97070 Ohm
-10 °C 55330 Ohm
-5 °C 42320 Ohm
0 °C 32650 Ohm
5 °C 25390 Ohm
10 °C 19900 Ohm
15 °C 15710 Ohm
20 °C 12490 Ohm
25 °C 10000 Ohm
30 °C 8057 Ohm
35 °C 6532 Ohm
40 °C 5327 Ohm
50 °C 3603 Ohm
60 °C 2488 Ohm
70 °C 1752 Ohm
80 °C 1258 Ohm
90 °C 918 Ohm
100 °C 680 Ohm
110 °C 511 Ohm
120 °C 389 Ohm
130 °C 301 Ohm
Table 10.2 Characteristics of VR 11 standard sensor