Operation Manual

4 On-roof fitting and installation
14 Installation manual auroTHERM exclusive 0020077994_02
4.1.1.3 Transporting collectors
1. To protect the collectors against damage, always trans-
port them when they are standing horizontally.
2. Transport the collectors to the roof using suitable aids.
4.1.2 Complying with clearances and installation
clearances
In order to fit the collectors correctly, the specified clear-
ances and installation clearances must be observed.
For the necessary edge clearances, see chapter "Defin-
ing edge clearances of the roof brackets".
4.1.3 Selecting suitable connection
Select the appropriate connection for the collectors.
Ensure that the solar fluid flows through the collectors
either from left to right or from right to left.
Conditions: Number of VTK 1140/2 collectors: 1 7
max. 7 x VTK 1140/2
Switch up to 7 VTK 1140/2 units in series (according to
the 14 m² aperture surface area).
Conditions: Parallel connection, aperture surface area: 7 m²
Always connect as many collectors as possible in series,
even when several collector rows are arranged on top of
each other.
Note
Up to an aperture surface area of 7 m²
(accordingly for 3 pcs VTK 1140/2 + 1 pc
VTK 570/2), you must switch the collectors
in series.
Conditions: Parallel connection, aperture surface area: 14 m²
Set up several parallel collector rows and connect these
hydraulically in parallel.
Always connect as many collectors (at least 7 m²) as
possible in series.